Series 8 Controller and I/O Specification, S803-150-500
TC, millivolt inputs
Temperature
stability
RTD inputs
Long term drift
Input impedance
CMV with respect to Power System
common, dc to 60 Hz
CMRR, 50 or 60 Hz (with 1000 ohms
source impedance max.)
Voltage, channel-to-channel, dc to 60
Hz
Voltage, channel-to-shield, dc to 60 Hz
Crosstalk, dc to 60 Hz
NMRR at 50/ 60 Hz
Line frequency integration
RTD sensor excitation current
Cold Junction Compensation Range
TC Linearization Accuracy
Open Thermocouple Detection
RTD Max Lead Resistance
Surge protection (sensor terminals)
Surge protection (power/serial link with
cable adapter option)
Supported RTD types
Supported Thermocouple types
Version 1
+/-20 ppm per deg C max
+/-20 ppm per deg C max
500 ppm
1 megohm at dc (TC only)
Channel to Shield :+/-250 VDC or VAC RMS
Channel to Channel: +/-33 VDC or VAC RMS
120 dB min
+/-33 VDC or VAC RMS
+/-250 VDC or VAC RMS
80 dB (120 dB at 50 and 60 Hz)
60 dB min
Fixed selection of 50 Hz or 60 Hz
1 milliamp
-20 to +60 deg C (± 0.5 deg C typical)
± 0.05 Ω / deg C
1
Each conversion qualified, ≤ 1000 Ω = guaranteed no-trip ≥ 1500 Ω
guaranteed trip.
15 Ω
EN 61000-4-5 (for Industrial locations, 1kV line to line, 2kV line to gnd.)
EN 61000-4-5 (for Industrial locations, 1kV line to line, 2kV line to gnd.)
Pt: 100 ohm DIN 4376
Pt: 100 ohm JIS C-1604
Pt: 1000 ohm
Ni: 120 ohm ED #7
Cu: 10 ohm SEER
Cu: 50 ohm SEER
ANSI specification J
ANSI specification K
ANSI specification E
ANSI specification T
-180 to +800 deg C
-180 to +650 deg C
-40 to +260
deg C
-45 to +315 deg C
20 to +250 deg C
-50 to +150 deg C
-200 to +1200 deg C
-100 to +1370 deg C
-200 to +1000 deg C
-230 to +400 deg C