Series 8 Controller and I/O Specification, S803-150-500
3.3.2.
Analog Input with HART – Single Ended
Function
The Analog Input Module accepts high level current inputs from transmitters and sensing devices.
Notable Features
Extensive self-diagnostics
Optional redundancy
HART-capable, multivariable devices
Fast loop scan
Internal or external field power selection
Detailed Specification- Analog Input with HART (8C-PAIHA1)
Parameter
Input / Output Module
IOTA Modules
Input Type
Input Channels
A/D Converter Resolution
1
Input Range
Voltage Rating
Module Current Rating
Common Mode Rejection Ratio, dc to
60 Hz (500 source imbalance)
Common Mode Voltage, dc to 60 Hz
Normal Mode Rejection Ratio, at 60 Hz
Normal Mode Filter Response
Maximum Normal Mode Input
Crosstalk, dc to 60 Hz (channel-to-
channel)
Maximum Input voltage (any input
referenced to common, no damage)
Input Scan Rate
Hardware Accuracy (@ CMV = 0 V)
Version 1
On board excitation power (no need for marshalling
power)
Suitable for Configure / Status for HART Device
Galvanic Isolation
Specification
8C-PAIHA1 - Analog Input with HART (16), Coated
8C-TAIXA1
Non Redundant, Coated
8C-TAIXB1
Redundant, Coated
Current (2-wire or self-powered transmitters)
16 Channels (Single Ended type)
16 bits
4-20 mA (through 250 Ω)
24 VDC
110 mA
70 dB
-6 to +5 V peak
19 dB
Single-pole RC, -3 dB @ 6.5 Hz
± 30 Volts
-60 dB
± 30 Volts
50 ms
± 0.075% of full-scale (23.5°± 2°C)
± 0.15% of full-scale (0 to 60°C)
20
6"
12''