Specifications. Next, measure the area occupied by the fireplace, note the floor construction and
consult your local building code to determine if additional support is needed.
6.2.1 RAISED BASE INSTALLATION OF MORE THAN 4" (R VALUE FOR THE HEARTH EXTENSION NOT
REQUIRED)
The Stratford may be installed directly on the floor or on a raised combustible or non combustible base. If
the fireplace is elevated more than 4" (B), an R value for the hearth extension is not required. However,
the upper and lower angle, for the full width of the floor protection, must be protected 2" horizontally and
vertically (E) by a non-combustible material. For example, a sheet metal (not included). Apart from these
two corners, the sheet metal does not have to cover the rest of the wall between the base of the fireplace
and the floor.
Note that the non-combustible hearth extension floor area must extend at least 16" (41 cm) in front of the
hearth as shown in Section 6.3.2: Minimum Hearth Extension Requirements.