2.3 CONFIGURATION USING AMS DEVICE MANAGER

With an AMS Device Manager software package, you can commission and configure the device, monitor
status and alerts, troubleshoot from the control room, perform advanced diagnostics, and automatically
document activities with a single application. Full configuration capability with AMS Device Manager
requires loading the most current Device Description (DD) for this device. Download the latest DD at
www.solahd.com
or Fieldcommgroup.org.

2.4 HART CONFIGURATION LOCk

The HART software lock prevents changes to the device configuration from all sources; all changes requested
via HART by the Field Communicator, AMS Device manager will be rejected. The HART Lock can be enabled or
disabled with a Field Communicator or AMS Device Manager.
PROCEDURE USING THE AMS DEVICE MANAGER
1. Right click on the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Select the Lock/Unlock button under HART Lock (Software) and follow the screen prompts.

2.5 BASIC CONFIGURATION OF COMMUNICATION MODULE

CONFIGURING THE DEVICE VARIABLES
Mapping HART variables using the Field Communicator The "Variable Mapping" menu displays the
sequence of the process variables. Select the sequence below to change this configuration.
The device allows selection of the Primary Variable (PV), Secondary Variable (SV), Tertiary Variable
(TV), and Quaternary Variable (QV). Variable choices are various parameters of the power supply units
connected to either Channel 1 or Channel 2 of the communication module. The following table lists
the selectable variables, ranges and units.
Table 2.5: Device Variables
Variable
Supply 1 Input Voltage
Supply 1 Output Voltage
Supply 1 Output Current
Supply 2 Input Voltage
Supply 2 Output Voltage
Supply 2 Output Current
Emerson.com/SolaHD
Range
0–300
0–32
0–40
0–300
0–32
0–40
2. CONFIGURATION
Units
V
V
A
V
V
A
8/2022
Page: 15