2.15 Oil management device – OM5 TraxOil™
The compressors in the Copeland CO
OM5 TraxOil oil level management system. This device is intended to prevent the compressors from
operating with insufficient oil by opening a valve which allows the oil to flow from the oil separator to
the compressor. The OM5 uses a hall sensor to measure the oil level. Unaffected by foaming oil or
light, a magnetic f loat changes its position according to the oil level. The hall sensor converts the
magnetic field changes into an equivalent signal, which is used by the integrated electronic controller
to monitor and display the actual oil level with LEDs.
In case of low oil level and after a delay time of 20 seconds the OM5 will generate an alarm which
will make the unit controller stop the compressor immediately.
This alarm can be displayed on the Visotouch like any other alarm of the unit.
Figure 35 below depicts the sight glass level control zones. Table 14 describes the LED code legend.
Figure 36 shows the OM5 TraxOil mounted on the compressor.

Figure 35: Sight glass level control zones

LEDs
Status
Oil level in green zone (60 - 40 %)
Oil level in green zone (60 - 40 %)
Oil level in yellow zone (40 - 25 %)
Oil level in red zone (25 - 0 %)
Table 14: LED code legend

Figure 36: OM5 TraxOil mounted on the compressor

26
scroll ref rigeration units are equipped with an Emerson
2
Function
OK
OK
Warning
Alarm
Alarm
Yes, delay
20 sec
AGL_Unit_OMTE_CO
_EN_Rev01