4. TROUBLESHOOTING
8/2022
PROCESS ALARMS
Process Alarm
Supply x
High Output Current Alarm
1
Supply x
High Temperature Alarm
1
Note
: X refers to power supply 1 or 2.
1
Page: 30
Probable Cause
Output current from the
power supply is exceeding the
configured alarm limit.
Power supply temperature
is exceeding the configured
alarm limit.
User Guide
Corrective Action(s)
Check the power supply load,
if nearing or crossing the load
capacity, distribute the load
among multiple supplies.
Increase the high current alarm
limit using AMS Device Manager
Check the power supply load,
if nearing or crossing the load
capacity, distribute the load
among multiple supplies.
Check ventilation and ambient
conditions for the power supply.
Increase the high temperature
alarm limit using AMS
device manager.
Emerson.com/SolaHD
A272-366