G3 Series EtherCAT

User Configurable Device Parameters

The Aventics' G3 EtherCAT
TM
certain instances. The following is a description of these device parameters.
Name
IP Address
Gateway IP
Params Lock
Config Lock
Diagnostic Word
I/O Diagnostic
Status
Output Fault
Action

Parameters Lock

This parameter lock is used to lock out changes to all node configuration parameters (except parameter lock). Once
the manifold is commissioned the Parameters lock should be set to "LOCKED" to ensure that parameters are not
unintentionally modified.

I/O Configuration Lock

This I/O configuration lock parameter is used to lock the I/O configuration of the manifold. The manifold's I/O
configuration map is determined on power-up of the node. Once the manifold is commissioned the I/O configuration
lock should be set to "LOCKED" to ensure the I/O will not re-map in the event of an I/O module failure. If an I/O
module fails with configuration locked the node will report an I/O module missing at the location of the failed module.

Communication Fault Mode Parameter

This parameter is used to describe characteristics or behaviors of output points (bits). The parameter shown below is
used to determine what state the outputs will have, during a "Fault" event. The Communication Fault Mode parameter
will allow control of all output points on the manifold.
The user, through PLC configuration settings, can determine how the outputs behave when a communication fault
action occurs. These settings are non-volatile and thus will not change upon loss of power.
The two behavior options are:
1.
Turn Off All Outputs
2.
Maintain Last Output State
node allows the user to set many user options which define how the manifold behaves in
Description
Sets the IP address to
access the node web
page
Set the Gateway
IP address
Selects Parameters
Locked/Unlocked
Selects I/O Configuration
Locked/Unlocked
Enables / Disables the
diagnostic word
Allocates I/O diagnostic
status bits
Determines whether to
use idle value attribute
or hold last state
TDG3ECM1-5EN
Subject to change without notice
www.asco.com/g3
Technical Manual
TM
Settable Via
Web
Display
Server
X
X
X
X
X
X
X
07/2020
13-145