Summary of Contents for Emerson SolaHD SCM-W-HRT7
Page 1
User Guide A272-366 Rev. 1.0 8/2022 HART Revision 7 Communication Module (SCM-W-HRT7) SCM SolaHD™ Communication Module For use with SolaHD™ SDN-D Power Supplies...
3.2 POwER SuPPLY PARAmETERS ANd mAxImum VALuES ..............21 3.3 SCm TEmPERATuRE VALuE ......................24 3.4 REVISION INFORmATION....................... 25 4. TROUBLESHOOTING ........................26 4.1 mASTER RESET ..........................31 4.2 TECHNICAL SuPPORT ........................31 4.3 wARRANTY ........................... 31 APPENDIx A: FIELD COMMUNICATOR MENU TREE ................32 Page: 2 Emerson.com/SolaHD...
User Guide REVISION HISTORY A272-366 8/2022 REVISION HISTORY Revision Code Revision Date Description Rev. 1.0 8/2022 Final Page: 3 Emerson.com/SolaHD...
8/2022 A272-366 PREFACE Thank you for purchasing SolaHd SCm-w-HRT7! This user manual defines how to use the communication functions of SCM-W-HRT7. It also contains important safety instructions that must be followed during the installation and operation of the communication module.
Risk of personal injury and explosion hazard when used in a Class I, Division 2/Class I, Zone 2 environment. Refer to the "Safety Instruction Sheet - SCM Communications Modules" provided with the product or located on our website at www.SolaHD.com. Be sure to adhere to all safety procedures provided in the sheet. Page: 5 Emerson.com/SolaHD...
SDN-D Documents & Drawings) • COMPATIBLE DEVICES/APPLICATIONS SCM-W-HRT7 is designed to support all SolaHD SDN-D power supplies. As a HART compliant device, it is designed to work with Emerson's DeltaV™, AMS Device Manager and TREX and other HART Masters. Page: 6 Emerson.com/SolaHD...
Either 1 or 2 SDN-D Power Supplies can be supported by a single SCM module. Power Supply Connection Power for SCM and power supply data are provided with included 8-inch cables. Network Connection and 2-wire terminal connection. Topologies supported Point-to-Point or Multidrop Page: 7 Emerson.com/SolaHD...
1. PRODUCT OVERVIEW User Guide 8/2022 A272-366 1.3 CONSTRUCTION Important parts of the HART communication module are as below. Figure 1.3: Parts of the HART Communication Module Page: 8 Emerson.com/SolaHD...
Section 1.3. The maximum cable length is 200 mm. Additional cables for interconnecting SCM to SOLA power supplies are available as a separate part. Figure 1.5.1: I2C Cable to Connect Power Supplies to Communication Module Page: 9 Emerson.com/SolaHD...
The HART loop can be either powered from the built in 24V supply in the HART IO module or this can be a separate power supply as illustrated in the figures below. Figure 1.5.3: Connection with DeltaV Traditional IO Page: 10 Emerson.com/SolaHD...
Each device is identified by a unique address (1–15) and responds to the commands defined in the HART protocol. Figure 1.5.4A: Establishing multi-drop communication Page: 11 Emerson.com/SolaHD...
Page 12
CHANGE TRANSMITTER ADDRESS USING AMS DEVICE MANAGER 1. Right click on the device and select Configure from the menu. 2. Select Manual setup. 3. In the HART tab, select the Change Polling Address button. Figure 1.5.4B: Change Polling Address Page: 12 Emerson.com/SolaHD...
1. PRODUCT OVERVIEW A272-366 8/2022 1.5.5 SPACING The setup below shows the spacing of the SCM-W-HRT7 to the SDN-D Power Supplies. Please note that all devices are mounted on a standard DIN-rail. FIgure 1.5.5: Spacing Emerson Classification: Internal Page: 13 Emerson.com/SolaHD...
Turn on the Field Communicator by pressing the ON/OFF key. The Field Communicator will search for a HART- compatible device and indicate when the connection is made. If the Field Communicator fails to connect, it indicates that no device was found. If this occurs, refer to Troubleshooting. Figure 2.2: Field Communicator Connections Page: 14 Emerson.com/SolaHD...
Table 2.5: Device Variables Variable Range Units Supply 1 Input Voltage 0–300 Supply 1 Output Voltage 0–32 Supply 1 Output Current 0–40 Supply 2 Input Voltage 0–300 Supply 2 Output Voltage 0–32 Supply 2 Output Current 0–40 Page: 15 Emerson.com/SolaHD...
The Tag is up to eight characters and the Long Tag (a parameter introduced with the HART 6 and 7 protocol) was extended to 32 characters long. Neither parameter has any impact on the primary variable readings of the transmitter, it is only for information. Page: 16 Emerson.com/SolaHD...
Page 17
2. In the left navigation pane select Manual Setup. 3. On the Device Tab there will be a group box called identification. Enter the desired characters in the Tag, Date, Descriptor, and Message fields 4. Select Apply when complete. Figure 2.6: Device Information Page: 17 Emerson.com/SolaHD...
CONFIGURING TEMPERATURE UNITS USING AMS DEVICE MANAGER 1. Right click on the device and select Configure. 2. Navigate to Guided Setup page and select the temperature unit of measurement. 3. Select Apply when complete. Page: 18 Emerson.com/SolaHD...
The accuracy defined in the table above is valid over the entire operating input, load, Vout range • and 0–60°C (unless specified otherwise) P1, P2 Temperature (power supply internal ambient temperature) accuracy at > 50°C • Iout accuracy at > 20% of max. operating load • Page: 19 Emerson.com/SolaHD...
Page 20
Byte 5:: Bit 2 Temperature Alarm configured alarm limit. Supply 2 High Power supply temperature exceeding the Byte 5:: Bit 3 Temperature Alarm configured alarm limit. (1) Location of the Alert in the HART command 48 Status field. Page: 20 Emerson.com/SolaHD...
EC - OVP Error count – Over Voltage Protection counter EC - PBoost Error count – Power Boost counter EC - InputApp Error count – Input Voltage Applied counter EC - OTP Error count – Over Temperature Protection counter Page: 21 Emerson.com/SolaHD...
Page 22
3. MONITORING User Guide 8/2022 A272-366 PROCEDURE USING THE AMS DEVICE MANAGER 1. Right click on the device and select Overview from the menu. 2. Under “Shortcuts” select Power Supply Parameters Figure 3.2A: Power Supply Parameters Page: 22 Emerson.com/SolaHD...
Page 23
User Guide 3. MONITORING A272-366 8/2022 Figure 3.2B: Max Values Page: 23 Emerson.com/SolaHD...
Temperature Data button for latest value. PROCEDURE USING THE AMS DEVICE MANAGER 1. Right click on the device and select Configure from the menu. 2. Select Manual Setup. 3. Select Field Replacement Unit Information. Figure 3.3 SCM Temperature Page: 24 Emerson.com/SolaHD...
The revision of the SCM, Power Supply and Device Description file can be displayed. PROCEDURE USING THE AMS DEVICE MANAGER 1. Right click on the device and select Overview. 2. Select Device Information. 3. Select Revisions Tab. Figure 3.4: Revision Information Page: 25 Emerson.com/SolaHD...
Current loop stuck at 4mA Check the power supply parameter assigned to the primary variable and Primary variable set to lowest make sure that its value is correct in possible value the range. Follow the power supply troubleshooting procedures. Page: 26 Emerson.com/SolaHD...
Page 27
Hart connection issues to scan the device wiring, loop resistance and possible (Communication Module). noise issues. Check if AMS-DM is set to scan multi drop devices in case the Polling address communication module is configured at non-zero polling address Page: 27 Emerson.com/SolaHD...
Page 28
Process the specific alert condition and its Alarm Status LED - Blinking Amber Alarm (see Process Alarms table) associated corrective action. condition belonging to the Also see the "Process Alarm" "Maintenance" classification section below. Page: 28 Emerson.com/SolaHD...
Page 29
SDN-D power NV Integrity Error factory default configuration for supplies and plugging them back. the device. If alert condition persists, replace the communication module. Note : X refers to power supply 1 or 2. Page: 29 Emerson.com/SolaHD...
Page 30
High Temperature Alarm is exceeding the configured Check ventilation and ambient alarm limit. conditions for the power supply. Increase the high temperature alarm limit using AMS device manager. Note : X refers to power supply 1 or 2. Page: 30 Emerson.com/SolaHD...
Security 3. Model 1. Device is Locked/Unlocked 2. Lock/Unlock Power Supply 2 1. Primary Power Supply Parameters 2. Secondary 1. Supply Parameters Supply Parameters 3. Model 2. Min Max Values 1. Supply Parameters (Grid) 2. Update Data Page: 32 Emerson.com/SolaHD...
Page 35
Note that unit specifications are subject to change without notice. TECHNICAL SUPPORT Website: www.solahd.com Technical Support E-Mail: solahd.technicalservices@emerson.com Toll-Free: (800) 377-4384 USA: (847) 268-6651 WARRANTy Please see the “Terms & Conditions of Sale” document within the UPS packaging. While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.