Example Universal Input 1 - Siemens 7MJ2000-1A 00 Series Operating Instructions Manual

Process monitoring for oscillating positive displacement pumps
Table of Contents

Advertisement

See also
Connecting acoustic emission sensors (Page 30)
6.6.2

Example universal input 1

Procedure
1. Connect the transmitter, as described in the "Connecting signal inputs" section.
2. Press the <PAR> button for 5 seconds. This opens the parameter menu.
3. Use the
4. Using the
5. Next the alarm limit is set. This is done via one of the parameters P.30 to P.33. Again use
6. Using the
7. As a final step, you must set the digital output at which the alarm is to be displayed. This
8. Using the
9. Press the <MEAS> button to return to the measuring menu.
Note
Alarm limit
The alarm limits set via parameters P.30 to P.33 are only effective with analog inputs. With
digital inputs, the values given in the "Specification" apply as switching thresholds.
See also
Connecting signal inputs (Page 31)
SITRANS DA400 for oscillating positive displacement pumps
Operating Instructions, 09/2008, A5E00841120-03
and
buttons to select the parameters P.26 to P.29 associated with the
universal input.
Example: If the external transmitter is connected to terminals 55 to 58, select parameter
P.26.
and
buttons, set the associated parameter value. If, for example, a
transmitter with an output signal 0 to 20 mA is connected, set the parameter value "0-20".
the
and
buttons, to select the associated parameter. In our example, parameter
P.30 is to be selected for universal input 1.
and
buttons, set the desired parameter value. The parameter value set is
displayed to the left in the middle section of the digital display.
is done via one of the parameters P.34 to P.37. Use the
associated parameter. In our example, parameter P.34 is to be selected for universal
input 1.
and
buttons, set the desired parameter value. For example, "do1" for
displaying the alarm at digital output 1.