6.4.2

Parameter list

Parameter
Parameter
no.
name
P. 0
SWREV
P. 1
SoCH1
P. 2
SoCH2
P. 3
SoCH3
P. 4
SoCH4
P. 5
PrAL1
P. 6
AL1
P. 7
PrAL2
P. 8
AL2
P. 9
PrAL3
P.10
AL3
P.11
PrAL4
P.12
AL4
P.13
TIME
P.14
AcK
P.15
doPR1
P.16
doAL1
P.17
doPR2
P.18
doAL2
P.19
doPR3
P.20
doAL3
SITRANS DA400 for oscillating positive displacement pumps
Operating Instructions, 09/2008, A5E00841120-03
Parameter value
2.01.00
oFF
on L
on H
on_L
on_H
SIMU
tESt
oFF, on L, on H
oFF, on L, on H
oFF, on L, on H
0 to 99.9
0 to 99.9
0 to 99.9
0 to 99.9
0 to 99.9
0 to 99.9
0 to 99.9
0 to 99.9
0 to 9999
oFF
¬St.Ac
St.Ac
oFF, do1, do2, do3, do4, do5,
do6, ¬do1, ¬do2, ¬do3, ¬d04,
¬do5, ¬do6
As P.15
As P.15
As P.15
As P.15
As P.15
Factory
Meaning
setting
SW version (not adjustable)
oFF
Acoustic channel 1
Channel switched off
Channel in measurement mode, normal
measuring sensitivity
Channel in measurement mode, normal
measuring sensitivity, pre and main alarm
received in event of sensor fault
Channel in measurement mode, measuring
sensitivity reduced by 20 dB
Channel in measurement mode, reduced
measuring sensitivity, pre and main alarm
received in event of sensor fault
Channel in simulation mode
Channel in test mode
oFF
Acoustic channel 2 / See P.1
oFF
Acoustic channel 3 / See P.1
oFF
Acoustic channel 4 / See P.1
99.9
Pre-alarm channel 1
99.9
Main alarm channel 1
99.9
Pre-alarm channel 2
99.9
Main alarm channel 2
99.9
Pre-alarm channel 3
99.9
Main alarm channel 3
99.9
Pre-alarm channel 4
99.9
Main alarm channel 4
0
Response time for alarms coming from
acoustic channels in seconds
oFF
Type of alarm acknowledgement
Alarm not stored, no acknowledgement
Alarm not stored, acknowledgement stops
until next response
Alarm stored, acknowledgement stops until
next response
oFF
Status signal assignment:
Pre-alarm 1 to hardware output
(do : digital output / ¬ : inverse)
do1
Main alarm 1
oFF
Pre-alarm 2
do2
Main alarm 2
oFF
Pre-alarm 3
do3
Main alarm 3
Operation