8.4.8
8 Analog Output
The ASTAT XL has an analog output, which can be connected to associated equipment to monitor
motor performance.
8A – Analog Output A
Options:
Description:
8B – Analog A Scale
Range:
Description:
8C – Analog A Maximum
Range:
Description:
8D – Analog A Minimum
Range:
Description:
8.4.9
9 Auto-Reset
The ASTAT XL can be programmed to automatically reset certain trips, which can help minimise
operating downtime. Trips are divided into three categories for auto-reset, depending on the risk to
the soft starter:
Group
A
B
C
Other trips cannot be automatically reset.
50
ASTAT XL User Manual
Current (% FLC)
(default)
Motor Temp (%)
Motor kW (%)
Motor kVA (%)
Motor pf
Measured motor kW:
Maximum motor kW:
Measured motor kVA: √3 x average current x mains reference voltage
Maximum motor kVA: √3 x motor FLC x mains reference voltage
Selects which information will be reported via the analog output.
0-20 mA
4-20 mA (default)
Selects the range of the analog output.
0% - 600%
Calibrates the upper limit of the analog output to match the signal measured
on an external current measuring device.
0% - 600%
Calibrates the lower limit of the analog output to match the signal measured
on an external current measuring device.
Current imbalance
Phase Loss
Power loss
Frequency
Undercurrent
Instantaneous overcurrent
Input A Trip
Motor overload
Motor thermistor
Heatsink Overtemperature
DET-812
Fout! Stijl niet gedefinieerd.
Current as a percentage of motor full load current.
Motor temperature as a percentage of the motor's
thermal capacity.
Measured motor kilowatts, as a percentage of
maximum kW.
Measured motor kilovolt amperes, as a percentage of
maximum kVA.
Motor power factor, measured by the soft starter.
√3 x average current x mains reference voltage x
measured power factor
√3 x motor FLC x mains reference voltage. Power
factor is assumed to be 1
Default:
Default:
100%
0%