OC_MV (Function ID: 440081)
Setting items
OC4-DPR
OC4-TMS-ORG
OC4-Rtimer
TOC4R
OC4-RTMS-
ORG
OC4-k
OC4-a
OC4-c
OC4-kr
OC4-b
Output
OC4-2fBlk
OC4-VTFBlk
OC4-OPMD
OC4-UseFor
OC4-ARCBlk
OC4-Act-Stop
OC4-Act-Start
OC4-Act-Run
Range
Unit
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of ORG inverse curve
DEF / DEP
- OC4 reset delay type of US
0.00 - 300.00
s OC4 definite time reset delay
OC4 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OC4 user original curve coefficient
0.00000 - 10.00000
- OC4 user original curve coefficient
0.00000 - 10.00000
- OC4 user original curve coefficient
0.00000 - 500.00000
- OC4 user original curve coefficient
0.00000 - 10.00000
- OC4 user original curve coefficient
Non / Block-AllP /
- OC4 operation block by 2f-detection
Block-PerP
Non / Block
- OC4 operation block by VTF
3POR / 2OUTOF3
- OC4 operation mode
Trip / Alarm
- OC4 used for trip or alarm
Non / Block
- Autoreclose block by OC4
Enabling OC4 calculation the motor when
Off / On
-
motor status is in stop status
Enabling OC4 calculation the motor when
Off / On
-
motor status is in start-up status
Enabling OC4 calculation the motor when
Off / On
-
motor status is in running status
- 37 -
Contents
6F2T0200 (0.15)
Default
Note
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
3POR
Trip
Block
Off
Off
Off
GRE200 (1,2)