Toshiba GR-200 Series Instruction Manual page 543

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

(iii)
CT for zero-phase sequence current for SEF
If the sensitive earth fault (SEF) function is provided, VCT will have Ise terminal. The user
can convert the polarity with setting [Pol-IseCT]=Negative.
Table 5.4-10 CT polarity styles of CT for zero-phase sequence current for SEF
Polarity
Setting
No.
[Pol-IseCT]
Style
Positive
321
Positive
polarity
Negative
322
Negative
polarity
Busbar
A B C
Inputted at No.7 terminal
Outputted at No. 8 terminal
Busbar
A B C
Inputted at No.8 terminal
Outputted at No. 7 terminal
- 524 -
Wiring examples
7
Ise
8
7
Ise
8
6F2T0200 (0.15)