Download Print this page

Toshiba GR-200 Series Instruction Manual page 477

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Input
Command "PLC-On-Control" with ILK†
(PLC#3 connection point)
512001 800301EE31
DEV01_OP_INTERLOCK
Command "PLC-On-Control" without ILK†
(PLC#4 connection point)
512001 800301EE30
DEV01_OP_COMMAND
ILK† condition ("Open") passed
DPOS01-Open
User configurable condition
(PLC#1 connection point)
512001 800301EE56
DPOS01IN_TMP_34
User configurable condition
(PLC#2 connection point)
512001 820301EE5E
DPOS01IN_TMP_42
Figure 4.1-30 Operate 'Off' by the PLC function in DPOS01
†Note: The ILK function can provide the criteria for operation for control of the "Off"
operation.
‡Note: An "operate condition" signal is generated in the operate-condition logic (see
Figure 4.1-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative "operate-condition" programmed by the user is required in place of
the signal generated by the original operate-condition logic, connect the
alternative "operate-condition" to the logic shown in Figure 4.1-30 using
connection point #1 "User configurable condition". That is set the scheme switch
[DPOS01-LGCTRCON] to PLC and use "DPOS01IN_TMP_34".
§§Note: The "DPOS01_OEX_BO" signal is issued when Fixedlogic is set for the scheme
switch [DPOS01-LGCFEXOT]. If the signal is to be issued from the programmed
logic by the user in place of the logic in Figure 4.1-20, connect the signal "Operate
completed" generated in the programmed logic to the connection point #2 "User
configurable condition". That is, set the scheme switch [DPOS01-LGCFEXOT] to
PLC and use "DPOS01IN_TMP_42".
*Note: The user can select a type of the output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting applied
to [DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
Operate logic in DPOS01
DPOS01 function (Function ID: 512001)
" DPOS01_FEC_OK_CSF"
(512001 8003011E7E)
Operate Cmd.
with ILK † condition
&
Operation Cmd.
without ILK † condition
[DPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[DPOS01-LGCFEXOT]
Fixedlogic
[DPOS01-PLSM]*
Var
Fix
Detection of state-change in a device
"DPOS01_FEC_OK_CSF"
(512001 8003011E7E)
- 458 -
" DPOS01_FEC_OK_CS"
(512001 8003011E81)
1≥
1≥
&
&
&
&
PLC#1
&
1≥
&
PLC#2
&
6F2T0200 (0.15)
Output
[DPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"DPOS01_FEX_BO"
(512001 8103011DD0)
&
Assign to BOs
To "Wait for a command"
" DPOS01_EX_CMP "
(512001 8003011E93)
Operate Completed
" DPOS01_EX_FFL "
[DPOS01-RST]
(512001 8603011E91)
0
t
1.0s- 100.0s
Operate Failed
††
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2