Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Setting of OVG_MV (Function ID: 462181)
Setting device
OVG4-DPR
OVG4-TMS
TOVG4R
ORG
OVG4
OVG4-DPR
OVG4-TMS
TOVG4R
Output
OVG4-VTFBlk
OVG4-UseFor
Range
Unit
10 - 100
% OVG4 drop-out/pick-up ratio
0.010 - 100.000
- OVG4 time multiplier (in IDMT mode)
0.0 - 300.0
s OVG4 definite time reset delay
1.0 - 220.0
V OVG4 threshold
10 - 100
% OVG4 drop-out/pick-up ratio
0.010 - 100.000
- OVG4 time multiplier (in ORG mode)
0.0 - 300.0
s OVG4 definite time reset delay
Non / Block
- OVG4 operation block by VTF
Trip / Alarm
- OVG4 used for trip or alarm
- 194 -
Contents
6F2T0200 (0.15)
Default
Note
100
1.000
0.0
20.0
100
1.000
0.0
Non
Trip
GRE200 (1,2)