Download Print this page

Toshiba GR-200 Series Instruction Manual page 847

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Oct.
Item
9
Cause of transmission (COT)
10
Common address of ASDU
11
Function type (FUN)
12
Information number (INF)
13
Double point information (DPI)
14
Millisecond (low)
15
Millisecond (high)
16
Minutes + Invalid flag (MSB)
17
Hours + Summer time flag (MSB)
18
Supplementary information (SIN)
19
Checksum
20
End
Table 11.5-4
Oct.
Item
1
Start
2
Length
3
Length
4
Start
5
Control field
6
Address
7
Type identification (Type ID)
8
Variable structure qualifier
9
Cause of transmission (COT)
10
Common address of ASDU
11
Function type (FUN)
12
Information number (INF)
13
Double point information (DPI)
14
Relative time (RET)
16
Fault number (FAN)
18
Millisecond
20
Minutes + Invalid flag (MSB)
21
Hours + Summer time flag (MSB)
22
Supplementary information (SIN)
23
Checksum
24
End
Description
A comment (less than 16 characters) can be set. This setting does not affect the function of
Value
1/9/11/12
1-254
0-255
0-255
/(0)/1/2/(3)/
0-59999
0-59+80H
0-23+80H
0-255
Time-tagged message with relative time (Type ID=2)
Value
08H+ACD
+DFC
1-254
1/9/11/12
1-254
0-255
0-255
/(0)/1/2/(3)/
0-65535
0-65535
0-59999
0-59+80H
0-23+80H
0-255
- 828 -
Remarks
Customized with GR-TIEMS
Linked with Address setting
Customized with GR-TIEMS
Customized with GR-TIEMS
-
Customized with GR-TIEMS
DP
16H
Remarks
68H
18
18
68H
Setting from the relay
2
Customized with GR-TIEMS
81H
Customized with GR-TIEMS
Linked with Address setting
Customized with GR-TIEMS
Customized with GR-TIEMS
-
Customized with GR-TIEMS
DP
Trigger condition to calculate
RET is customized with GR-
TIEMS.
Trigger condition of FAN
increment is customized with
GR-TIEMS.
16H
6F2T0200 (0.15)
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2