GOOSE receiving block (GOSUBBLK)
(ii)
This is used for receiving or rejecting GOOSE subscription information from another IED for
the test of bad receptions. See Chapter
(→p. 778).
Test flag cancel (S-TestFlagCancel)
(iii)
Test flag in the communication packet will be removed unconditionally, when On is set for
setting [Test flag].
Test for all communication (TestFlag-EN)
(iv)
Setting [TestFlag-EN]=On allows to set test flags at all communication protocol.
Test for relay application
14.4.2
Auto monitoring function (A.M.F)
(i)
Issuing alarms will be blocked when Off is set for [A.M.F]. For the content about the monitoring
function, see Chapter
Test of cold load protection (CLP-Test)
(ii)
STATE0 or STATE3 will be selected temporally, if STATE0 or STATE3 is set for setting [CLP-
TEST]. See Chapter
Thermal overload function test (THM-Test, THM-IP)
(iii)
Setting [THM-Test]=On allows to have a test value for the pre-load current (Ip). The Ip value
is discussed in Chapter
SOTF test (SOTF-Test)
(iv)
Setting [SOTF-Test]=On allows to generate the cold load condition mandatorily for testing,
which is discussed in Chapter
Under voltage test (UV,UVS-Test)
(v)
Settings [UV-Test] and [UVS-Test]=On is not to operate UV and UVS blocking elements for
testing. See Chapter
143 or 155).
ARC shot number test (SHOTNUM-Test)
(vi)
Setting [SHOTNUM-Test] is provided so that the user can have the preferred shot number for
the ARC test, which is discussed in Chapter
Communication protocol: IEC 61850 communication
Automatic supervision function
Relay application: Cold load protection
Relay application: Thermal overload function
Relay application: Switch on to fault
Relay application: Phase
- 924 -
(→p.
).
677
for more detail (→p. 131).
Phase-to-phase under-voltage protection
or
Relay application: Autoreclose
6F2T0200 (0.15)
(→p. 123).
(→p. 114).
(→p. 233).
GRE200 (1,2)
(→p.

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2