8.7.4

Data formats 15 to 24

The table below shows the format (15) "trip log". It contains the last 5 tripping operations with
time stamp and source.
Table 8- 45
Byte
12-19
24-31
36-43
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02
Format (15) "trip log"
Bit
0-7
Time
Time stamp of the 1st tripping operation
8
Reserved 0x00
9
Reason for
Reason for trip of 1st tripping operation
tripping
1 = overload
operation
2 = instantaneous Short circuit
3 = delayed Short-circuit
4 = Ground fault
5 = Ext. protection function
6 = Overload N-conductor
7 = ETU self-protection (analog override)
8 = Overtemperature
20 = Unbalance Current
21 = Unbalance Voltage
22 = Active power in normal dir.
23 = Active power in reverse dir.
24 = Overvoltage
25 = Undervoltage
26 = Overfrequency
27 = Underfrequency
28 = THD current
29 = THD voltage
30 = Change in phase dir. of rot.
10
Source of 1st tripping operation
14 = Meter. function/M. PLUS
25 = Trip unit
11
Reserved 0x00
Time stamp of 2nd tripping operation
20
Reserved 0x00
21
Reason for 2nd tripping operation
22
Source of 2nd tripping operation
23
Reserved 0x00
Time stamp of 3rd tripping operation
32
Reserved 0x00
33
Reason for 3rd tripping operation
34
Source of 3rd tripping operation
35
Reserved 0x00
Time stamp of 4th tripping operation
44
Reserved 0x00
45
Reason for 4th tripping operation
46
Source of 4th tripping operation
47
Reserved 0x00
Meaning
Data library
8.7 Formats
259