3VL molded-case circuit breaker
4.2 COM20 connection
Table 4- 3
Connection of the motorized operating mechanism, SENTRON VL
L2–
S2A
S2B
L1+
PE
Table 4- 4
Technical data of the COM20 PROFIBUS module
Permissible ambient
temperature
Installation altitude above sea
level
Weight
Degree of protection according
to IEC 60529
Shock resistance (sine pulse)
Mounting position
Immunity to electromagnetic
interference according to IEC
60947-1
Immunity to electromagnetic
interference according to IEC
60947-1
Safe isolation according to IEC
60947-1
Fixing
Indicator
100
Motor
X20.1
X20.2
X20.3
X20.4
X20.5
In operation
During storage and transportation
Permissible max. ambient temperature +50 °C (no
safe isolation)
Conducted interference; burst according to IEC
61000-4-4
Conducted interference; high-frequency according
to IEC 61000-4-6
Conducted interference; surge according to IEC
61000-4-5
Electrostatic discharge; ESD according to IEC
61000-4-2
Field-based interference suppression; radiated
immunity according to IEC 61000-4-3
Conducted and radiated interference emission
All circuits are safely isolated from the control circuit for the motor operator in accordance
with IEC 60947-1 (terminal SEO (ON), SEO (OFF), L1+), that is, dimensioned with double
creepages and clearances
Snap-mounted to 35 mm DIN rail or screw fixing via additional push-in lugs
Green/red/yellow "Device" LED
COM20
SEO (ON)
SEO (OFF)
L1+
-25 °C...+70 °C, no condensation
-40 °C...+80 °C
< 2000 m
< 3000 m
approx. 0.28 kg
IP20
100 m/s
220 m/s
Arbitrary
2 kV (power ports)
2 kV (signal ports)
10 V
1 kV (line to ground)
8 kV (air discharge)
4 kV (contact discharge)
10 V/m
DIN EN 55011, A
/DIN EN 55022, A
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02
Power supply
DC
AC
GND
N
L+
L
PE
PE
20 ms
2
11 ms
2
Green: Ready
Red: Function test negative,
device disabled
Yellow: Memory submodule or
addressing plug detected
Off: No control supply voltage