PROFIBUS data transfer
6.7 Setting and changing the PROFIBUS address of the COM15/COM20
1. A dialog box then opens in which you can select, via the relevant application access point
and the selected PROFIBUS DP interface, the currently effective PROFIBUS DP address
of the slave whose address is to be changed. 126 must be selected on the new
PROFIBUS DP modules COM20/COM15.
2. Click on OK to load all parameters including the communication parameters from the
device into Switch ES Power where they can be changed.
3. In the tree on the left side, select the point "Communication" and select the desired new
address in the drop-down field.
4. In the "Target System" menu, select the entry "Load in Switching Device". This transfers
all parameters currently displayed in Switch ES Power to the circuit breaker.
The figure below shows how the PROFIBUS address and the content of the cyclic data
traffic can be set with the help of Switch ES Power.
132
NOTICE
Write protection
Without the wire jumper "DPWriteEnable", the PROFIBUS write protection on the
COM15 is active and the changes will not be adopted.
3WL/3VL circuit breakers with communication capability - PROFIBUS