8.6.4
Data set DS 52 main overview 1
The table below contains the data sets DS52: Main overview 1 (length 16 bytes, read-only):
Table 8- 17
Content of data set 52
Byte
0
Current value phase 1
2
Current value phase 2
4
Current value phase 3
6
Present maximum current of the phase with
maximum load
8
Current value N conductor (trip unit)
10
Current value ground fault (trip unit)
12
Warnings and setpoints in the communication
module
14
Current at the moment of shutdown
16
Phase at the moment of shutdown
17
Reserved
19
Switches and indicates the current parameter
set
20
Reserved
22
Status of the circuit breaker
23
Tripping operations, basic protection function,
last trip
24
Number of the phase with maximum load
25
Position of circuit breaker
26
Mean value of all phases
28
Long-time mean value of 3-phase current
30
Phase unbalance current in %
31
Maximum phase unbalance current in %
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02
Description
Data
Source
Source
point
WL
VL
380
—
ETU
381
—
ETU
382
—
ETU
374
—
ETU
375
—
ETU
376
—
ETU
402
—
ETU
403
—
ETU
404
—
ETU
—
—
—
370
—
ETU
—
—
—
328
—
ETU
401
—
ETU
373
—
ETU
24
—
ETU
383
—
ETU
193
—
ETU
172
—
ETU
437
—
ETU
Data library
8.6 Data sets
Format
Length
Scaling
(bits)
unsigned
16
int
unsigned
16
int
unsigned
16
int
unsigned
16
int
unsigned
16
int
unsigned
16
int
Format
16
—
(402)
unsigned
16
int
Format
8
—
(373)
unsigned
16
—
char
Format
1
—
(370)
unsigned
16
—
char
Format
8
—
(328)
Format
8
—
(401)
Format
3
—
(373)
Format
4
—
(24)
unsigned
16
int
unsigned
16
int
unsigned
8
char
unsigned
8
char
0
0
0
0
0
0
0
0
0
0
0
203