Data Set Ds 73 Min. And Max. Measured Values Of The Voltages - Siemens SENTRON VL Series System Manual

Circuit breakers with communication capability - profibus
Hide thumbs Also See for SENTRON VL Series:
Table of Contents

Advertisement

Data library
8.6 Data sets
8.6.9

Data set DS 73 min. and max. measured values of the voltages

The table below shows the content of data set 73 in which the minimum and maximum
measured values of the voltages are transmitted. It also contains the associated time stamps
for these minimum and maximum measured values.
The table below contains the data sets DS73: Min./max. measured values of the voltages
and the associated time stamps (length 174 bytes, read-only):
Table 8- 22
Content of data set 73
Byte
0
Minimum phase-to-phase voltage between
phase L1 and L2
2
Maximum phase-to-phase voltage between
phase L1 and L2
4
Minimum phase-to-phase voltage between
phase L2 and L3
6
Maximum phase-to-phase voltage between
phase L2 and L3
8
Minimum phase-to-phase voltage between
phase L3 and L1
10
Maximum phase-to-phase voltage between
phase L3 and L1
12
Minimum of the neutral point voltage
phase L1
14
Maximum of the neutral point voltage
phase L1
16
Minimum of the neutral point voltage
phase L2
18
Maximum of the neutral point voltage
phase L2
20
Minimum of the neutral point voltage
phase L3
22
Maximum of the neutral point voltage
phase L3
24
TS minimum phase-to-phase voltage
between phase L1 and L2
32
TS maximum phase-to-phase voltage
between phase L1 and L2
40
TS minimum phase-to-phase voltage
between phase L2 and L3
48
TS maximum phase-to-phase voltage
between phase L2 and L3
56
TS minimum phase-to-phase voltage
between phase L3 and L1
64
TS maximum phase-to-phase voltage
between phase L3 and L1
214
Description
Data point
Source
WL
205
Meter. fct.
206
Meter. fct.
207
Meter. fct.
208
Meter. fct.
209
Meter. fct.
210
Meter. fct.
211
Meter. fct.
212
Meter. fct.
213
Meter. fct.
214
Meter. fct.
215
Meter. fct.
216
Meter. fct.
37
COM15
38
COM15
39
COM15
40
COM15
41
COM15
42
COM15
3WL/3VL circuit breakers with communication capability - PROFIBUS
Source
Format
Length
VL
(bits)
unsigned
int
unsigned
int
unsigned
int
unsigned
int
unsigned
int
unsigned
int
unsigned
int
unsigned
int
unsigned
int
unsigned
int
unsigned
int
unsigned
int
Time
Time
Time
Time
Time
Time
System Manual, 03/2011, A5E01051353-02
Scaling
16
0
16
0
16
0
16
0
16
0
16
0
16
0
16
0
16
0
16
0
16
0
16
0
64
64
64
64
64
64