Mandik MSD Technical Documentation Manual

Mandik MSD Technical Documentation Manual

Multi smoke damper
Hide thumbs Also See for MSD:

Advertisement

Quick Links

TPM 159/22
Version 2022-12-20
MSD
Multi smoke damper
Technical Documentation
Installation, Commissioning, Operation, Maintenance and Service Manual
www.mandik.co.uk
Manufacturer
MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz
Authorized representative
MANDIK UK Ltd • 130 Aztec West • Bristol BS32 4UB • United Kingdom • Tel.: +44 117 4526376 • E-Mail: help@mandik.co.uk

Advertisement

Table of Contents
loading

Summary of Contents for Mandik MSD

  • Page 1 Manufacturer MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz Authorized representative MANDIK UK Ltd • 130 Aztec West • Bristol BS32 4UB • United Kingdom • Tel.: +44 117 4526376 • E-Mail: help@mandik.co.uk...
  • Page 2: Table Of Contents

    TPM 159/22 These technical specifications state a row of manufactured sizes and models of multi smoke dampers MSD. It is valid for production, designing, ordering, delivery, maintenance and operation. CONTENT I. GENERAL.....................................3 Description....................................3 Design.....................................4 Design with actuating mechanism............................4 Communication and control module MDCM........................9 Communication and control module MDPM........................9...
  • Page 3: General

    TPM 159/22 I. GENERAL Description Smoke extraction dampers - MSD are designed into an inlet or extract smoke ventilation system. The dampers are designed either to close to provide compartmentalization or to open (for fresh air inlet) or to allow removal of the heat and combustible products from a fire in the affected fire zone/compartment.
  • Page 4: Design

    “potential-free” BS EN8519. limit switches. The actuator for operating the damper blade is mounted ■ in an insulated cover/box. It is accessible after removing Actuating mechanism Design .44, .54 and .65 Page 4 MSD - multi smoke damper Version 2022-12-20...
  • Page 5 (BEN 24-ST) with plug Cable 1 m, 6 x 0,75 mm Cable 1 m, 6 x 0,75 mm - auxiliary switch connectors * Only available for 24V and selected damper sizes Version 2022-12-20 MSD - multi smoke damper Page 5...
  • Page 6 (BEE 24-ST) with plug Cable 1 m, 6 x 0,75 mm Cable 1 m, 6 x 0,75 mm - auxiliary switch connectors * Only available for 24V and selected damper sizes Page 6 MSD - multi smoke damper Version 2022-12-20...
  • Page 7 -30°C … +55°C Storage temperature -40°C … +80°C Cable 1 m, 3 x 0,75 mm Connection - drive Cable 1 m, 6 x 0,75 mm - auxiliary switch (BE 24-ST) with plug connectors Version 2022-12-20 MSD - multi smoke damper Page 7...
  • Page 8 16 W (start at -20°C) Protection class Degree of protection IP 66 Adjustment time for 95° < 60 s Ambient temperature -40°C … +50°C Storage temperature -40°C … +70°C Cable 1 m, 0,5 mm Connection Page 8 MSD - multi smoke damper Version 2022-12-20...
  • Page 9: Communication And Control Module Mdcm

    Drive open / close 230v Damper actuator Comms IN Communications loop cable CAT 3 or equivalent 1.5mm 2 core screened Comms OUT 230mm x 160mm x 62mm deep steel enclosure powder coated red - IP54 Version 2022-12-20 MSD - multi smoke damper Page 9...
  • Page 10: Dimensions

    → see pages 47 to 48 Actuating mechanism Damper blade Access door/ inspection cover MSD with actuating mechanism, protective cladding boards and insulation box X = 168mm - BEN (BEE) 171mm - BE 220mm - SCHISCHEK Y = 250mm - BEN (BEE)
  • Page 11 TPM 159/22 MSD with actuating mechanism and insulation box X = 168mm - BEN (BEE) 171mm - BE 220mm - SCHISCHEK Y = 250mm - BEN (BEE) 260mm - BE 260mm - SCHISCHEK Z = 300mm - BEN (BEE) 370mm - BE 430mm - SCHISCHEK MSD - design „IB‟...
  • Page 12: Technical Parameters

    280 x – 0,0799 20,1 – 0,0482 16,2 – 0,0892 21,3 – 0,0562 16,9 – 0,0910 21,5 – 0,0615 17,5 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 12 MSD - multi smoke damper Version 2022-12-20...
  • Page 13 0,2140 29,5 0,2046 30,3 – 0,2314 30,8 0,2196 31,6 – 0,2445 31,8 355 x 180 – 0,0381 15,7 0,2532 32,4 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2022-12-20 MSD - multi smoke damper Page 13...
  • Page 14 (15 N.m) – 0,1809 27,4 – 0,1156 23,9 – 0,2082 29,2 – 0,1346 25,1 – 0,2354 30,9 – 0,1473 25,9 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 14 MSD - multi smoke damper Version 2022-12-20...
  • Page 15 48,8 (40 N.m) – 0,4974 48,4 (25 N.m) 750 x 180 – 0,0823 22,9 0,5151 49,3 BELIMO BEN (15 N.m) Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2022-12-20 MSD - multi smoke damper Page 15...
  • Page 16 74,4 – 0,2865 39,6 0,9534 75,1 – 86,5 0,3050 40,5 1,0128 77,9 – 106,5 0,3544 1,0870 88,3 SCHISCHEK InMax 50.75 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 16 MSD - multi smoke damper Version 2022-12-20...
  • Page 17: Placement And Assembly

    The damper must be installed so that the entire damper blade - in A+100 the closed position - is located inside the fire separating structure (wall) and at the same time the control mechanism and inspection openings are freely accessible. Version 2022-12-20 MSD - multi smoke damper Page 17...
  • Page 18: Statement Of Installations

    EI 90 (h i↔o) S1500C HOT400/30AAmulti Ablative Coated Batt Vertical duct installation – MULTI / MULTI EI 120 (v i↔o) S1500C HOT400/30AAmulti Insulation with ROCKWOOL FIREPRO Horizontal duct installation – MULTI / MULTI Page 18 MSD - multi smoke damper Version 2022-12-20...
  • Page 19: Installation In Solid Wall Construction Single / Multi

    + Firestop acrylic SMOKE sealant HILTI CFS-S ACR or equivalent) Fire stop coating thickness 1 mm (e.g. HILTI CFS-CT, PROMASTOP-CC or equivalent) Fixing profile with threaded rod → see pages 27 to 30 Version 2022-12-20 MSD - multi smoke damper Page 19...
  • Page 20 British gypsum thistle bond 60 (or equivalent can by used) minimum density 670 kg/m³) Fixing profile with threaded rod → see pages 27 to 30 ROCKWOOL FIREPRO DuctRock Slab th. 90 mm acc. to EN 1366-8 ROCKWOOL FIREPRO Glue Page 20 MSD - multi smoke damper Version 2022-12-20...
  • Page 21 Fire stop coating thickness 1 mm (e.g. HILTI CFS-CT, PROMASTOP-CC or equivalent) Fixing profile with threaded rod → see pages 27 to 30 ROCKWOOL FIREPRO DuctRock Slab th. 90 mm acc. to EN 1366-8 ROCKWOOL FIREPRO Glue Version 2022-12-20 MSD - multi smoke damper Page 21...
  • Page 22: Installation In Gypsum Wall Single / Multi

    + Firestop acrylic SMOKE sealant HILTI CFS-S ACR or equivalent) Fire stop coating thickness 1 mm (e.g. HILTI CFS-CT, PROMASTOP-CC or equivalent) Fixing profile with threaded rod → see pages 27 to 30 Page 22 MSD - multi smoke damper Version 2022-12-20...
  • Page 23 British gypsum thistle bond 60 (or equivalent can by used) minimum density 670 kg/m³) Fixing profile with threaded rod → see pages 27 to 30 ROCKWOOL FIREPRO DuctRock Slab th. 90 mm acc. to EN 1366-8 ROCKWOOL FIREPRO Glue Version 2022-12-20 MSD - multi smoke damper Page 23...
  • Page 24 Fire stop coating thickness 1 mm (e.g. HILTI CFS-CT, PROMASTOP-CC or equivalent) Fixing profile with threaded rod → see pages 27 to 30 ROCKWOOL FIREPRO DuctRock Slab th. 90 mm acc. to EN 1366-8 ROCKWOOL FIREPRO Glue Page 24 MSD - multi smoke damper Version 2022-12-20...
  • Page 25: Installation In Solid Ceiling Construction Single / Multi

    + Firestop acrylic sealant HILTI CFS-S ACR or equivalent) Fire stop coating thickness 1 mm (e.g. HILTI CFS-CT, PROMASTOP-CC or equivalent) Fixing profile with threaded rod → see pages 27 to 30 Version 2022-12-20 MSD - multi smoke damper Page 25...
  • Page 26: Installation In Solid Ceiling Construction Multi / Multi

    Stone wool bound with use of an organic resin with crushed stone as a refrigerant, min. density 300 kg/m³ composed of two layers 2x60 mm Fixing profile with threaded rod → see pages 27 to 30 Page 26 MSD - multi smoke damper Version 2022-12-20...
  • Page 27: Suspension Systems

    TPM 159/22 Suspension systems Suspension MSD installed in vertical duct MULTI / MULTI EIS 120 The dampers and duct must be suspended separately. ■ Duct from BS EN 12101-7 in Steel (insulated or spray coated) ■ Example of connection to duct →...
  • Page 28 TPM 159/22 Suspension MSD installed in horizontal duct MULTI / MULTI EIS 120 The dampers and duct must be suspended separately. ■ Duct from BS EN 12101-7 in Steel (insulated or spray coated) ■ Example of connection to duct → see pages 32 to 38 ■...
  • Page 29 Washer for M8 - M20 Coupling Nut M8 - M20 Anchor Hinge plate - min. thickness 10 mm Concrete screw tested for fire resistance R30-R90, max. Tension up to 0.75 KN (length 35 mm) Version 2022-12-20 MSD - multi smoke damper Page 29...
  • Page 30 Bored plate HILTI MQZ-L or equivalent Dimension elements of the suspension system Washer for M8 - M20 ■ acc. to the weight of the damper, → see page 29 Nut M8 - M20 Page 30 MSD - multi smoke damper Version 2022-12-20...
  • Page 31: Duct Connection

    * min. one connection must be electrically conductive Connecting air duct MULTI Flange of MSD Flange of duct M8 bolt assembly - MSD damper are equipped with rivet nuts on the flanges* Ceramic self-adhesive tape (FJ 120 Pyrosil B 170-250 kg/m - Tremco-illbruck) or equivalent Lock washers...
  • Page 32: Msd Installed In Fire Separating Construction And Connection To Steel Duct

    MSD installed in fire separating construction and connection to steel duct Connection MSD to steel duct, installed in construction with gypsum filling and insulation - design "A" Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with nails and welding pins at max. spacings of 250 mm.
  • Page 33 TPM 159/22 Connection MSD to steel duct, installed in construction with Ablative Coat. B. filling and insulation - design "A1" Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with nails and welding pins at max. spacings of 250 mm.
  • Page 34 TPM 159/22 Connection MSD to steel duct, installed in construction with gypsum filling and insulation - design "IB" Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with nails and welding pins at max. spacings of 250 mm.
  • Page 35 TPM 159/22 Connection MSD to steel duct, installed in construction with gypsum filling and insulation - design "IB" Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with nails and welding pins at max. spacings of 250 mm.
  • Page 36 TPM 159/22 Connection MSD to steel duct, installed in construction with Ablative Coat. B. filling and insulation - design "IB1" Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with nails and welding pins at max. spacings of 250 mm.
  • Page 37 TPM 159/22 Connection MSD to steel duct, installed in construction with Ablative Coat. B. filling and insulation - design "IB1" Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with nails and welding pins at max. spacings of 250 mm.
  • Page 38: Msd Installed In Steel Duct With Insulation

    MSD installed in steel duct with insulation Connection MSD in steel duct with insulation - design "IB1" Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with nails and welding pins at max. spacings of 250 mm.
  • Page 39: Technical Data

    ρ [kg/m air density ξ coefficient of local pressure loss for the nominal damper section → see page 40 Determination of pressure loss by using diagram ρ = 1,2 kg/m Version 2022-12-20 MSD - multi smoke damper Page 39...
  • Page 40 0,2429 0,2397 0,2226 0,2204 0,2076 0,2065 0,2044 0,1947 0,1905 1400 0,2611 0,2397 0,2375 0,2204 0,2183 0,2044 0,2033 0,2022 0,1926 0,1894 1500 0,2589 0,2386 0,2365 0,2183 0,2161 0,2022 0,2012 0,2001 0,1905 0,1883 Page 40 MSD - multi smoke damper Version 2022-12-20...
  • Page 41: Noise Data

    -24,1 -33,2 -5,2 -3,9 -4,3 -6,4 -10,1 -15,6 -22,7 -31,5 -5,5 -4,1 -5,9 -9,4 -14,6 -21,5 -5,9 -4,1 -5,6 -8,9 -13,8 -20,4 -28,8 -6,2 -4,3 -3,9 -5,3 -8,4 -13,1 -19,5 -27,6 Version 2022-12-20 MSD - multi smoke damper Page 41...
  • Page 42: Material, Finishing

    The actuator cover is made of fire-resistant material (fire protection board). ■ IV. INSPECTION, TESTING The appliance is constructed and preset by the manufacturer, its operation is dependent on proper installation and ■ adjustment. Page 42 MSD - multi smoke damper Version 2022-12-20...
  • Page 43: Transportation And Storage

    Manual operation ■ Without power supply, the damper can be operated ■ manually and fixed in any required position. Version 2022-12-20 MSD - multi smoke damper Page 43...
  • Page 44: Electrical Connection Of The Actuator In Protection Box

    Seal up the space around cable with fire resistant mastic (HILTI CFS-S ACR, PROMASTOP) or equivalent. Let the mastic harden. ■ example drilled holes Example of position of holes in the wall of the box, without pre-manufactured slot Page 44 MSD - multi smoke damper Version 2022-12-20...
  • Page 45: Connection Of The Control Module Mdpm & Mdcm Interfaces Inside Protection Box

    Seal up the space around cable with fire resistant mastic (HILTI CFS-S ACR, PROMASTOP) or equivalent. ■ Let the mastic harden. ■ Drilling areas for routing the connection cable of modul to the actuator Dimensions of protection box Version 2022-12-20 MSD - multi smoke damper Page 45...
  • Page 46: Entry Into Service And Revisions

    Dampers blades should open and close correctly and operation should be visually inspected and documented prior to handover. Inspection hole detail Spare parts Spare parts are supplied only on basis of an order. ■ Page 46 MSD - multi smoke damper Version 2022-12-20...
  • Page 47: Product Data

    Schematic examples of use individual designs ("A", "A1", "IB", "IB1") → see page 48 EXAMPLE: MSD 800x400 - .44 A - 800x400-damper size, .44-damper design, A-individual design Dampers design Additional digit with actuating mechanism BEN, BEE, BE, InMax 50.75-S for 230V with actuating mechanism BEN, BEE, BE, InMax 50.75-S for 24V...
  • Page 48: Methods Of Damper Installation, According To Design

    + Firestop acrylic sealant HILTI CFS-S ACR or equivalent) Fire stop coating thickness 1 mm (e.g. HILTI CFS-CT, PROMASTOP-CC or equivalent) MULTI Fire Compartment ROCKWOOL FIREPRO DuctRock Slab th. 90 mm Page 48 MSD - multi smoke damper Version 2022-12-20...
  • Page 49 Manufacturer MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz Authorized representative MANDIK UK Ltd • 130 Aztec West • Bristol BS32 4UB • United Kingdom • Tel.: +44 117 4526376 • E-Mail: help@mandik.co.uk...

Table of Contents