    These technical specifications state a row of manufactured sizes and models of multi smoke dampers (further only dampers) MSD. It is valid for production, designing, ordering, delivery, maintenance and operation. 1. Description......................... 2. Design..........................3. Dimensions, weights......................16 4. Placement and Assembly....................31 5.
  • Page 3 Cycling test without load (possible design .4M0, .4M1, .5M0 and .5M1) Dampers MSD can be open against flow and pressure. Dampers MSD-W has to be open with the help of flow or without flow present. Damper characteristics • CE certified acc. to EN 12101-8 •...
  • Page 4 Working conditions Exact damper function is provided under the following conditions: a) maximum air velocity 15 m/s b) un derpressure max. -1500 Pa or overpressure max. 500 Pa. Dampers can be installed in arbitrary position (horizontal or vertical blade axis). Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.
  • Page 5 MSD AC/DC 24 V AC/DC 24 V AC 230 V Power voltage 50/60Hz 50/60Hz 50/60Hz Power consumption - in operation - in the end position 0,1 W 0,3 W 0,4 W Dimensioning 6 VA (Imax 8,2 A @ 5 ms) 6,5 VA (Imax 8.2 A @ 5 ms)
  • Page 6 MSD AC/DC 24 V AC/DC 24 V AC 230 V Power voltage 50/60Hz 50/60Hz 50/60Hz Power consumption - in operation 2,5 W 3,5 W - in the end position 0,1 W 0,3 W 0,4 W Dimensioning 5 VA (Imax 8,2 A @ 5 ms) 5,5 VA (Imax 8.2 A @ 5 ms)
  • Page 7 AC/DC 24 V AC 230 V Power voltage 50/60Hz 50/60Hz Power consumption - in operation 12 W - in the end position 0,5 W 0,5 W Dimensioning 18 VA (Imax 8,2 A @ 5 ms) 15 VA (Imax 7,9 A @ 5 ms) Protection class Degree of protection IP 54...
  • Page 8 24-240 VAC/DC Nominal voltage 50/60Hz Power consumption - motoring 10 W - heating 16 W (start at -20°C) Protection class Degree of protection IP 66 Running time for 95° < 60 s Ambient temperature range -40°C … +50°C Non-operating temperature -40°C …...
  • Page 9 Design with the communication and supply device BKNE 230-24 Design with communication and power supply device BKNE 230-24 and with actuator BEN (BEE, BE)-ST for 24V. The BKNE 230-24 serves on the one hand as a decentralized network device for powering the actuator and on the other hand transmits the signal of the communication and control device BKSE 24-6.
  • Page 10 Communication and supply device Power voltage AC 230V 50/60Hz Power consumption 10 W (including actuator) Dimensioning 19 VA (including actuator) Protection class Ambient operation temperature -30°C … +50°C Storage temperature -40°C … +80°C Connection - network cable 1 m without plug - drive 6-pin plug, 3-pin plug - terminal blocks...
  • Page 11 Communication and control devices indicates operating condition and faults of flue dampers. These conditions can be signalled or transmitted to the higher-level control system via the auxiliary built-in contacts. Signals from individual BKNE 230-24 are evaluated separately. All BKNE 230-24 are controlled simultaneously.
  • Page 12 Design with electric actuating mechanism with emergency function and electromagnet MSD-W is always equipped by electric actuating mechanism BFN 230-T, BFN 24-T, DAF2.20S or DAF1.20S (further only "actuating mechanism") and is complemented with initiation by means of an electromagnet (solenoid). After being connected to power supply AC/DC 24V or 230V, the actuating mechanism displaces the damper blade into operation position "CLOSED"...
  • Page 13 AC 24V 50/60Hz Nominal voltage AC 230 V 50/60Hz DC 24 V Power consumption - motoring - holding 2,5 W 7 VA (Imax 150 mA @ 10 ms) Dimensioning 7 VA (Imax 5,8 A @ 5 ms) Protection class Degree of protection IP 54 Running time - motor <...
  • Page 14 AC 24V 50/60Hz Nominal voltage AC 230 V 50/60Hz DC 24 V Power consumption - motoring 26 VA (AC); 15,6 W (DC) 0,15 A - holding 9,3 VA (AC); 2,6 W (DC) 0,09 A Dimensioning 14 VA 14 VA Protection class Degree of protection IP 54 Running time - motor...
  • Page 15 Nominal voltage AC 230 V / 50 Hz Dimensioning 1,2 A Degree of protection IP 40 Ambient temperature -10°C … +40°C range Connecting cable 1m, 3x0,75mm AC 24 V / 50 Hz Nominal voltage DC 24 V Dimensioning Degree of protection IP 40 Ambient temperature -10°C …...
  • Page 16 Dimensions Position: Actuating mechanism Damper blade Access door/ inspection cover Position: Actuating mechanism Damper blade Access door/ inspection cover Electromagnet (solenoid) Pulse switch SIEM24...
  • Page 17 168 / 171 / 220 * 300 / 370 / 430 * Position: Insulation box Damper blade Access door/ inspection cover Protective cladding boards 168 / 171 / 220 * 300 / 370 / 430 * Position: Insulation box Damper blade Access door/ inspection cover...
  • Page 18 Position: Actuating mechanism Damper blade Access door/ inspection cover Position: Actuating mechanism Damper blade Access door/ inspection cover Electromagnet (solenoid) Pulse switch SIEM24...
  • Page 19 Weight and effective area - square dampers 0,0162 11,2 BELIMO BEN 11,7 BELIMO BFN 12,2 BELIMO BEN 0,0191 11,6 BELIMO BEN 12,1 BELIMO BFN 12,6 BELIMO BEN 41,5 0,0228 12,1 BELIMO BEN 12,6 BELIMO BFN 13,1 BELIMO BEN 0,0264 12,6 BELIMO BEN 13,1 BELIMO BFN...
  • Page 20 0,0984 21,4 BELIMO BEN 21,9 BELIMO BFN 22,4 BELIMO BEN 0,1040 22,1 BELIMO BEN 22,6 BELIMO BFN 23,1 BELIMO BEN 0,1077 22,5 BELIMO BEN BELIMO BFN 23,5 BELIMO BEN 0,1169 23,6 BELIMO BEN JOVENTA DAFx.20S 24,6 BELIMO BEN 0,1188 23,9 BELIMO BEN 26,2 JOVENTA DAFx.20S...
  • Page 21 0,0880 BELIMO BEN 19,5 BELIMO BFN BELIMO BEN 0,1012 20,3 BELIMO BEN 20,8 BELIMO BFN 21,3 BELIMO BEN 0,1145 21,6 BELIMO BEN 22,1 BELIMO BFN 22,6 BELIMO BEN 0,1277 22,8 BELIMO BEN 23,3 BELIMO BFN 23,8 BELIMO BEN 0,1304 23,1 BELIMO BEN 25,4 JOVENTA DAFx.20S...
  • Page 22 0,0619 16,7 BELIMO BEN 17,2 BELIMO BFN 17,7 BELIMO BEN 0,0721 17,6 BELIMO BEN 18,1 BELIMO BFN 18,6 BELIMO BEN 0,0789 18,2 BELIMO BEN 18,7 BELIMO BFN 19,2 BELIMO BEN 86,5 0,0840 18,6 BELIMO BEN 19,1 BELIMO BFN 19,6 BELIMO BEN 106,5 0,0976 19,7...
  • Page 23 0,2967 34,6 BELIMO BEN 36,9 JOVENTA DAFx.20S 35,6 BELIMO BEN 0,3184 37,2 BELIMO BEN 38,5 JOVENTA DAFx.20S 38,2 BELIMO BEE 0,0543 17,4 BELIMO BEN 17,9 BELIMO BFN 18,4 BELIMO BEN 0,0640 18,1 BELIMO BEN 18,6 BELIMO BFN 19,1 BELIMO BEN 41,5 0,0761 18,9...
  • Page 24 0,2899 33,5 BELIMO BEN 35,8 JOVENTA DAFx.20S 34,5 BELIMO BEN 0,3063 34,6 BELIMO BEN 36,9 JOVENTA DAFx.20S 35,6 BELIMO BEN 0,3172 35,3 BELIMO BEN 37,6 JOVENTA DAFx.20S 36,3 BELIMO BEN 0,3444 37,1 BELIMO BEN 39,4 JOVENTA DAFx.20S 38,1 BELIMO BEN 0,3499 38,4 BELIMO BEN...
  • Page 25 0,2108 28,7 BELIMO BEN 31,1 JOVENTA DAFx.20S 29,7 BELIMO BEN 0,2426 30,7 BELIMO BEN JOVENTA DAFx.20S 31,7 BELIMO BEN 0,2743 32,6 BELIMO BEN JOVENTA DAFx.20S 33,6 BELIMO BEN 0,3061 34,6 BELIMO BEN 36,9 JOVENTA DAFx.20S 35,6 BELIMO BEN 0,3124 BELIMO BEN 37,3 JOVENTA DAFx.20S BELIMO BEN...
  • Page 26 0,1338 BELIMO BEN 25,5 BELIMO BFN BELIMO BEN 0,1558 26,3 BELIMO BEN 26,8 BELIMO BFN 27,3 BELIMO BEN 0,1705 27,1 BELIMO BEN 27,6 BELIMO BFN 28,1 BELIMO BEN 86,5 0,1815 27,8 BELIMO BEN 28,3 BELIMO BFN 28,8 BELIMO BEN 106,5 0,2109 29,5 BELIMO BEN...
  • Page 27 0,6036 53,1 BELIMO BEN 54,4 JOVENTA DAFx.20S 54,1 BELIMO BE 0,6478 55,5 BELIMO BEN 56,8 JOVENTA DAFx.20S 56,5 BELIMO BE 0,1103 26,4 BELIMO BEN 26,9 BELIMO BFN 27,4 BELIMO BEN 0,1300 27,6 BELIMO BEN 28,1 BELIMO BFN 28,6 BELIMO BEN 41,5 0,1546 BELIMO BEN...
  • Page 28 0,6570 BELIMO BEN 59,3 JOVENTA DAFx.20S BELIMO BE 0,6941 59,8 BELIMO BEN 61,1 JOVENTA DAFx.20S 60,8 BELIMO BE 0,7188 61,1 BELIMO BEN 62,4 JOVENTA DAFx.20S 62,1 BELIMO BE 0,7805 64,1 BELIMO BEN 65,4 JOVENTA DAFx.20S 65,1 BELIMO BE 0,7929 64,8 BELIMO BEN 66,1 JOVENTA DAFx.20S...
  • Page 29 Weight and effective area - round dampers BELIMO BFN BELIMO BEN 0,0160 11,3 BELIMO BFN BELIMO BEN 0,0208 11,7 BELIMO BFN 10,1 BELIMO BEN 0,0277 12,2 BELIMO BFN 10,7 BELIMO BEN 0,0356 12,9 BELIMO BFN 11,4 BELIMO BEN 17,5 0,0463 13,6 BELIMO BFN 12,5...
  • Page 30 For square damper the open damper blade overlaps the damper body by the value “c” or “a” and “c”. These values are specified in the Tab. 3.2.1. For round damperthe open damper blade overlaps the damper body by the value “f” These values are specified in the Tab.
  • Page 31 Multi smoke extraction dampers are designed to remove heat and combustion products (e.g. smoke) from fire compartments according EN1366-8. Multi smoke extraction dampers are designed to horizontal or vertical installation with arbitrary blade axis position. To provide needed access space to the control device, all other objects must be situated at least 350 mm from the control parts of the damper.
  • Page 32 The control mechanism has to be protected (covered) against damage and pollution during installation process. During installation the damper blade must be in position “CLOSED”. The damper body should not be deformed in the course of installation. Once the damper built in, its blade should not grind on the damper casing during opening or closing.
  • Page 33 Mortar or gypsum Weichschott / Ablative Coated Batt Insulation with stone wool - mortar or gypsum Insulation with cement-lime plates - mortar or gypsum Insulation with stone wool - Weichschott / Ablative Coated Batt Insulation with cement-lime plates - Weichschott / Ablative Coated Batt Mortar or gypsum EI 120, min.
  • Page 34 ≥ 50 Position: Solid wall construction separating FIRST fire compartment from following compartment ≥ 100 Mortar or gypsum ≥ 50 Position: Solid wall construction separating FIRST fire compartment ≥ 100 from following compartment Mortar or gypsum...
  • Page 35 Position: Solid wall construction separating FIRST fire compartment from following compartment Fire resistant board / Ablative Coated Bat ≥ 100 Fire stop coating thickness 1 mm...
  • Page 36 Position: Solid wall construction separating two fire compartments Mortar or gypsum ≥ 100 Stone wool bound with use of an organic resin with crushed stone as a refrigerant, min. density 300 kg/m³ composed of two layers 2x60 mm Position: Solid wall construction separating two fire compartments Mortar or gypsum PROMATECT L500 - min.
  • Page 37 Position: Solid wall construction separating two fire compartments Fire resistant board / Ablative Coated Bat ≥ 100 Fire stop coating thickness 1 mm Stone wool bound with use of an organic resin with crushed stone as a refrigerant, min. density 300 kg/m³ composed of two layers 2x60 mm Position: Solid wall construction separating two fire compartments...
  • Page 38 ≥ 50 * EI 120, min. 125 mm Position: Gypsum wall construction separating FIRST fire compartment from following compartment Mortar or gypsum ≥ 50 * EI 120, min. 125 mm Position: Gypsum wall construction separating FIRST fire compartment from following compartment Mortar or gypsum...
  • Page 39 * EI 120, min. 125 mm Position: Gypsum wall construction separating FIRST fire compartment from following compartment Fire resistant board / Ablative Coated Bat Fire stop coating thickness 1 mm...
  • Page 40 Position: Gypsum wall construction separating two fire compartments Mortar or gypsum Stone wool bound with use of an organic resin with crushed stone as a refrigerant, min. density 300 kg/m³ * EI 120, min. 125 mm composed of two layers 2x60 mm Position: Gypsum wall construction separating two fire compartments Mortar or gypsum...
  • Page 41 Position: Gypsum wall construction separating two fire compartments Fire resistant board / Ablative Coated Bat Fire stop coating thickness 1 mm Stone wool bound with use of an organic resin with crushed stone as a refrigerant, min. density 300 kg/m³ composed of * EI 120, min.
  • Page 42 ≥ 50 * min. 110 - Concrete/ min. 125 - Aerated concrete Position: Solid ceiling construction separating FIRST fire compartment from following compartment Mortar or gypsum Duct ≥ 50 * min. 110 - Concrete/ min. 125 - Aerated concrete Position: Solid ceiling construction separating FIRST fire compartment from following compartment Mortar or gypsum...
  • Page 43 * min. 110 - Concrete/ min. 125 - Aerated concrete Position: Solid ceiling construction separating FIRST fire compartment from following compartment Fire resistant board / Ablative Coated Bat Fire stop coating thickness 1 mm...
  • Page 44 * min. 110 - Concrete/ min. 125 - Aerated concrete Position: Solid ceiling construction separating two fire compartments Mortar or gypsum Stone wool bound with use of an organic resin with crushed stone as a refrigerant, min. density 300 kg/m³ composed of two layers 2x60 mm Position: * min.
  • Page 45 * min. 110 - Concrete/ min. 125 - Aerated concrete Position: Solid ceiling construction separating two fire compartments Fire resistant board / Ablative Coated Bat Fire stop coating thickness 1 mm Stone wool bound with use of an organic resin with crushed stone as a refrigerant, min.
  • Page 46 Position: Duct Fixing profile with threaded rod min. 100 PROMATECT MS - th. min 40 mm, min. density 750 kg/m Protection cladding-boards are in line with blade – it is a part of the damper in designs A1 and IB1 Protection box of actuator - part of the IB and IB1 damper design Note: There is no protection box in designs A and A1.
  • Page 47: Design

    Position: Duct Fixing profile with threaded rod PROMATECT MS - th. min 40 mm, min. density 750 kg/m Stone wool bound with use of an organic resin with crushed stone as a refrigerant, min. density 300 kg/m³, thickness 60 mm Protection box of actuator - part of the IB and IB1 damper design Note: There is no protection box in designs A and A1.
  • Page 48 Position: Duct min. 100 Fixing profile with threaded rod PROMATECT MS - th. min 40 mm, min. density 750 kg/m Protection cladding-boards are in line with blade – it is a part of the damper in designs A1 and IB1 Protection box of actuator - part of the IB and IB1 damper design Note: There is no protection box in designs A and A1.
  • Page 49 Position: Duct Fixing profile with threaded rod PROMATECT MS - th. min 40 mm, min. density 750 kg/m Stone wool bound with use of an organic resin with crushed stone as a refrigerant, min. density 300 kg/m³, thickness 60 mm Protection box of actuator - part of the IB and IB1 damper design Note: There is no protection box in designs A and A1.
  • Page 50 In case of installation in dampers must be suspended using threaded rods and fixing profiles. Their dimensioning depends on the damper's weight (see. 6.6.) The dampers and duct must be suspended separately. Position: Fire separating construction separating first fire compartment from following compartment Fixing profile with threaded rod Position:...
  • Page 51 The dampers must be suspended using threaded rods and mounting profiles. Their dimensioning depends on the damper's weight. The dampers and duct must be suspended separately. The connected duct must be suspended in such a way that the transfer of all loads from the adjoining ventilation duct to the damper body is completely excluded.
  • Page 52: Pressure Loss

    Pressure loss calculation [Pa] pressure loss [m.s ] air flow speed in nominal damper section [kg.m ] air density coefficient of local pressure loss for the nominal damper section (see Tab. 8.1.1. and 8.2.1.) Determination of pressure loss by using diagram = 1,2 kg.m...
  • Page 53 Coefficient of local pressure loss - square dampers 2,1314 1,6906 1,3782 1,1149 1,0037 0,9288 0,7918 0,6827 0,6003 0,5350 1,9945 1,5804 1,2423 1,0368 0,9748 0,8785 0,7383 0,6367 0,5585 0,4976 1,9207 1,5162 1,1256 0,9994 0,9341 0,8442 0,7137 0,6078 0,5329 0,4772 1,8415 1,4584 1,1032 0,9651 0,9009...
  • Page 54 Coefficient of local pressure loss - round dampers 3,546 2,124 1,291 0,877 0,609 0,438 0,328 0,255 0,205 0,173 0,147 0,127 Level of acoustic output corrected with filter A. + 10 log(S) + K [dB(A)] level of acoustic output corrected with filter A [dB] level of acoustic output L related to the 1 m section (see Tab.
  • Page 55 11,5 14,7 16,9 20,1 22,3 24,1 27,2 29,4 31,2 32,6 33,8 16,7 22,1 25,3 27,5 30,7 32,9 34,6 37,8 40,0 41,7 43,2 44,4 24,2 29,6 32,8 35,0 38,1 40,4 42,1 45,3 47,5 49,2 50,7 51,9 30,0 35,4 38,6 40,8 44,0 46,2 47,9 51,1...
  • Page 56: Material

    Damper bodies are supplied in the standard design made of galvanized plate without any other surface finish. Damper blades are made of fire resistant asbestos free boards made of mineral fibres. Fasteners is galvanized. According to the customer's requirements, damper can be made of stainless material. Specifications for stainless-steel models –...
  • Page 57: Assembly

    The appliance is constructed and and preset by the manufacturer, its operation is dependent on proper installation and adjustment. Dampers are transported by box freight vehicles without direct weather impact, there must not occur any sharp shocks and ambient temperature must not exceed +50°C. Dampers must be protected against mechanic damages when transported and manipulated.
  • Page 58 Drill two holes into the protection box (from outside to inside) and pull through field wiring cables (fire resistant cables) to connect actuator trailing lead. Protection box is made of calcium silicate plates. Use drill (drill size acc. To suit connecting cable Ø + 2 mm for seal up by mastic) and make two holes (see fig.
  • Page 59: Spare Parts

    Before entering the dampers into operation after assembly and after sequential revisions, checks and functionality tests of all designs including operation of the electrical components must be done. After entering into operation, these revisions must be done according to requirement set by national regulations.
  • Page 60 Dobříšská 550, 267 24 Hostomice, Czech Republic DIMENSION: ACTUATING SYSTEM: WEIGHT (kg): YEAR/SER.NO.: MANUAL FIRE PROTEC. CLASS: TPM 109/15 Cert. No.: 1391-CPR-2021/0084, DoP: PM/MSD/01/21/2 EN 12101-8:2011 1391 MANDÍK, a.s. Dobříšská 550, 267 24 Hostomice, Czech Republic DIMENSION: ACTUATING SYSTEM: WEIGHT (kg): YEAR/SER.NO.:...
  • Page 61 Smoke damper MSD technical specifications design does not include protection box of the actuator and does not include protective cladding boards in line with the blade design does not include protection box of the actuator and includes protective cladding boards in line with the blade...
  • Page 62 Smoke damper MSD-W technical specifications design size - square (rectangular) - round type with actuating mechanism BEN, BEE, BE, InMax 50.75-S for 230V with actuating mechanism BEN, BEE, BE, InMax 50.75-S for 24V with the communication and supply device BKNE 230-24 and actuating mechanism BEN (BEE, BE)-ST for 24V .66*...