TPM 156/22 These technical specifications state a row of manufactured sizes and models of Multi compartment smoke control damper SEDM. It is valid for production, designing, ordering, delivery, maintenance and operation. CONTENT I. GENERAL.....................................3 Description....................................3 II. DESIGN.......................................4 Design with actuating mechanism............................4 Communication and control module MDCM........................9...
TPM 156/22 I. GENERAL Description Dampers - SEDM are designed into an inlet or extract smoke ventilation system. The dampers are designed either to close to provide compartmentalization or to open (for fresh air inlet) or to allow removal of the heat and combustible products from a fire in the affected fire zone/compartment.
The actuator for operating the damper blade is mounted ■ in an insulated cover/box. It is accessible after removing Insulated cover/box Actuating mechanism Design .44, .54 and .65 Page 4 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 5
(BEN 24-ST) with plug Cable 1 m, 6 x 0,75 mm Cable 1 m, 6 x 0,75 mm - auxiliary switch connectors * Only available for 24V and selected damper sizes Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 5...
Page 6
(BEE 24-ST) with plug Cable 1 m, 6 x 0,75 mm Cable 1 m, 6 x 0,75 mm - auxiliary switch connectors * Only available for 24V and selected damper sizes Page 6 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 7
Storage temperature -40°C … +80°C Cable 1 m, 3 x 0,75 mm Connection - drive Cable 1 m, 6 x 0,75 mm - auxiliary switch (BE 24-ST) with plug connectors Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 7...
Page 8
Protection class Degree of protection IP 66 Adjustment time for 95° < 60 s Ambient temperature -40°C … +50°C Storage temperature -40°C … +70°C Cable 1 m, 0,5 mm Connection Page 8 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Damper actuator Comms IN Communications loop cable CAT 3 or equivalent 1.5mm 2 core screened Comms OUT 230mm x 160mm x 62mm deep steel enclosure powder coated red - IP54 Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 9...
B+80 (140*) (106*) SEDM Actuating mechanism Damper blade Access door/ inspection cover Dimensions with actuating mechanism InMax 50.75S. Flange** ** If it is necessary, arbitrary flange could be removed. Page 10 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 11
Values “e” and “f” - with flange Values "a","c","e" and "f", has to be respected when projecting related smoke exhaust ducts. Flange with corner hole Flanges of dampers are 30 mm wide with oval hole. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 11...
BELIMO BEN 225 x (15 N.m) 47,7 51,4 0,0264 49,0 52,9 0,0295 50,0 54,0 0,0318 52,5 56,8 0,0380 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 12 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 13
60,8 65,8 0,0714 64,2 69,4 0,0819 67,5 72,9 0,0924 68,3 73,7 0,0945 70,9 76,6 0,1029 72,9 78,8 0,1092 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 13...
Page 14
0,1470 84,2 91,0 0,1568 87,8 94,8 0,1691 BELIMO BEE 94,6 102,3 0,1936 (25 N.m) 1000 101,7 109,7 0,2181 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 14 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 15
BELIMO BEN 450 x 58,1 62,9 0,0532 (15 N.m) 60,5 65,4 0,0646 62,0 67,1 0,0722 63,2 68,4 0,0779 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 15...
Page 16
74,3 80,1 0,1392 78,3 84,5 0,1632 82,4 88,9 0,1872 86,5 93,3 0,2112 87,4 94,1 0,2160 90,6 97,5 0,2352 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 16 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 17
111,0 0,3127 104,1 111,9 0,3180 107,5 115,5 0,3392 BELIMO BEE 111,8 120,0 0,3657 (25 N.m) 121,6 130,4 0,4187 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 17...
Page 18
68,8 70,3 0,0725 BELIMO BEN 700 x (15 N.m) 71,0 72,6 0,0882 73,8 75,4 0,1071 75,6 77,2 0,1197 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 18 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 19
80,6 87,1 0,1666 84,7 91,4 0,1972 89,3 96,2 0,2312 93,8 101,0 0,2652 98,4 105,8 0,2992 99,4 106,8 0,3060 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 19...
Page 20
128,6 0,4482 126,2 135,1 0,4897 127,2 136,2 0,4980 BELIMO BE (40 N.m) 131,3 140,4 0,5312 136,3 145,7 0,5727 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 20 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 21
94,0 100,4 0,1062 BELIMO BEN 1250 x 97,0 103,6 0,1357 (15 N.m) 100,1 106,7 0,1652 103,7 110,4 0,2006 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 21...
Page 22
129,6 139,7 0,4147 (25 N.m) 136,3 146,5 0,4862 142,8 153,4 0,5577 150,7 161,5 0,6292 BELIMO BE (40 N.m) Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 22 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 23
185,6 197,8 0,9792 192,5 205,0 1,0557 214,1 227,1 1,2087 SCHISCHEK InMax 50.75 (75 N.m) 1000 228,0 241,4 1,3617 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 23...
■ With smoke control ducting then refer to duct manufacturers tested parameters for spacing & pattress requirements. ■ No other services should pass through the dampers building work opening. Page 24 Multi compartment smoke control damper - SEDM Version 2024-06-26...
& EI performance on both sides). The smoke control damper can be integrated into a gypsum wall construction with fire classification EI120 or EI 90. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 25...
Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing. Page 26 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 27...
Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing. Page 28 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Seal all joints (Overplating strips, Spacing strips ■ with SEDM damper) with Promat glue K84. Examples of anchors to the fire dividing con- ■ struction →...
Page 30
Seal all joints (Overplating strips, Spacing strips ■ with SEDM damper) with Promat glue K84. Examples of anchors to the fire dividing con- ■ struction →...
Page 31
2 dampers on top of each other - solid wall - Ablative Coated Batt system Seal all joints (Overplating strips, Spacing strips ■ with SEDM damper) with Promat glue K84. Examples of anchors to the fire dividing con- ■ struction →...
Page 32
EI 120 S 4 dampers - gypsum wall - Ablative Coated Batt system Seal all joints (Overplating strips, Spacing strips ■ with SEDM damper) with Promat glue K84. Examples of anchors to the fire dividing con- ■ struction → see pages 37 to 41 ■...
→ see pages 43 to 44 ■ SEDM Smoke extraction duct Fixing profile with threaded rod → see page 36 Connection´s insulation L-holder → see pages 37 to 41 Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 33...
Page 34
→ see pages 43 to 44 ■ SEDM Smoke extraction duct Fixing profile with threaded rod → see page 36 Connection´s insulation L-holder → see pages 37 to 41 Page 34 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Coupling Nut M8 - M20 84,3 Anchor Hinge plate - min. thickness 10 mm Concrete screw tested for fire resistance R30-R90, max. Tension up to 0.75 KN (length 35 mm) Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 35...
Page 36
Flange of SEDM Flange of duct Self-tapping screw 5x30 mm and 1 pcs large washer M5 (for additional fixing, prevents the damper from sliding off the support - not necessary use) Page 36 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 37
TPM 156/22 Fixing SEDM according to size, with L-holder - tested fixing on wall / ceiling FOR: A < 500 B ≥ 500 FOR: A < 500 B < 500 FOR: A ≥ 500 B ≥ 500 From inner edge of the damper to...
Page 38
M8 bolt assemply (bolt min. M8x60 mm, 2 pcs large washer M8, nut M8) or equivalent Anchor → see page 35 Fixing profile with threaded rod → see page 36 Page 38 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 39
TPM 156/22 Fixing SEDM according to size - tested fixing to solid / gypsum or ceiling wall FOR: A < 500 B ≥ 500 FOR: A < 500 B < 500 FOR: A ≥ 500 B ≥ 500 From inner edge of the damper to the center of the holder, on both sides / opposite sides (mirrored) 1 holder to CENTER damper part "A"...
Page 40
TPM 156/22 Fixing SEDM to the solid (ceiling) wall construction with Ablative Coated Batt system * ATTENTION TO THE LOCATION OF THE JOINT ! Screws and nuts must not impede the free rotation of Blades. Solid wall construction SEDM Ablative Coated Batt Fixing element/steel holder for connecting damper to the wall (optional accessories MANDIK, a.s.
Page 41
SEDM Ablative Coated Batt Fixing element/steel holder for connecting damper to the wall (optional accessories MANDIK, a.s. or sheet metal min. thickness 2 mm and min. width 60 mm) Screw UNI 6x60 mm Installation hols The method of mounting must meet the ■...
M8 bolt assemply (bolt M8x20 mm, 2 pcs large washer M8, nut M8) * Ceramic self-adhesive tape (FJ 120 Pyrosil B 170-250 kg/m - Tremco-illbruck) or equivalent Lock washers Page 42 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Page 43
TPM 156/22 Example of connection SEDM damper in steel duct MULTI with insulation ROCKWOOL FIREPRO DuctRock Slab Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with screws and welding pins at max. spacings of 250 mm.
Page 44
TPM 156/22 Example installed SEDM damper in fire separating construction and connection to steel duct MULTI Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with screws and welding pins at max. spacings of 250 mm. Board joints must be covered using ROCKWOOL black aluminium foil tape. Follow duct supplier's instructions and insulation.
For KMM grille ensure blade overlaps do not strike KMM- spacer duct may be required - not included in delivery. ■ Free area value for KMM is 78%. ■ SEDM with cover grille without flange SEDM with cover grille and with flange Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 45...
→ see page 47 Determination of pressure loss by using diagram ρ = 1,2 kg/m air flow speed w [m/s] Page 46 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Dampers must be protected against impact when Another required packaging system should be approved ■ transported and manipulated. and agreed by manufacturer. Packaging material is not Page 54 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Seal up the space around cable with fire resistant mastic (HILTI CFS-S ACR, PROMASTOP) or equivalent. ■ Let the mastic harden. ■ example drilled holes Example of position of holes in the wall of the box, without pre-manufactured slot Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 55...
For installation, drill 4 holes in the rear of the housing (from inside to outside) with a maximum hole diameter of 8,5mm, ■ use fixing appropriate for the application. Seal all holes and gap between FIRE RATED housing and wall with firestop (HILTI CFS-S ACR, PROMASTOP). Page 56 Multi compartment smoke control damper - SEDM Version 2024-06-26...
Dampers blades should open and close correctly and op- eration should be visually inspected and documented prior to handover. Inspection hole detail Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 57...
P - with flanges design size AxB EXAMPLE: SEDM 180x355 .44/P - 180x355-damper size, .44-damper design, P-with flanges Dampers design Additional digit with actuating mechanism BEN, BEE, BE, InMax 50.75-S for 230V with actuating mechanism BEN, BEE, BE, InMax 50.75-S for 24V with actuating mechanism BEN (BEE)-SR for 24V .65*...
Page 59
Manufacturer MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz Authorized representative MANDIK UK Ltd • 130 Aztec West • Bristol BS32 4UB • United Kingdom • Tel.: +44 117 4526376 • E-Mail: help@mandik.co.uk...
Need help?
Do you have a question about the SEDM and is the answer not in the manual?
Questions and answers