Multi compartment smoke control damper
Hide thumbs Also See for SEDM:

Advertisement

Quick Links

TPM 156/22
Version 2024-06-26
SEDM
Multi compartment smoke control damper
Technical Documentation
Installation, Commissioning, Operation, Maintenance and Service Manual
www.mandik.co.uk
Manufacturer
MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz
Authorized representative
MANDIK UK Ltd • 130 Aztec West • Bristol BS32 4UB • United Kingdom • Tel.: +44 117 4526376 • E-Mail: help@mandik.co.uk

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SEDM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mandik SEDM

  • Page 1 Manufacturer MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz Authorized representative MANDIK UK Ltd • 130 Aztec West • Bristol BS32 4UB • United Kingdom • Tel.: +44 117 4526376 • E-Mail: help@mandik.co.uk...
  • Page 2: Table Of Contents

    TPM 156/22 These technical specifications state a row of manufactured sizes and models of Multi compartment smoke control damper SEDM. It is valid for production, designing, ordering, delivery, maintenance and operation. CONTENT I. GENERAL.....................................3 Description....................................3 II. DESIGN.......................................4 Design with actuating mechanism............................4 Communication and control module MDCM........................9...
  • Page 3: General

    TPM 156/22 I. GENERAL Description Dampers - SEDM are designed into an inlet or extract smoke ventilation system. The dampers are designed either to close to provide compartmentalization or to open (for fresh air inlet) or to allow removal of the heat and combustible products from a fire in the affected fire zone/compartment.
  • Page 4: Design

    The actuator for operating the damper blade is mounted ■ in an insulated cover/box. It is accessible after removing Insulated cover/box Actuating mechanism Design .44, .54 and .65 Page 4 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 5 (BEN 24-ST) with plug Cable 1 m, 6 x 0,75 mm Cable 1 m, 6 x 0,75 mm - auxiliary switch connectors * Only available for 24V and selected damper sizes Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 5...
  • Page 6 (BEE 24-ST) with plug Cable 1 m, 6 x 0,75 mm Cable 1 m, 6 x 0,75 mm - auxiliary switch connectors * Only available for 24V and selected damper sizes Page 6 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 7 Storage temperature -40°C … +80°C Cable 1 m, 3 x 0,75 mm Connection - drive Cable 1 m, 6 x 0,75 mm - auxiliary switch (BE 24-ST) with plug connectors Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 7...
  • Page 8 Protection class Degree of protection IP 66 Adjustment time for 95° < 60 s Ambient temperature -40°C … +50°C Storage temperature -40°C … +70°C Cable 1 m, 0,5 mm Connection Page 8 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 9: Communication And Control Module Mdcm

    Damper actuator Comms IN Communications loop cable CAT 3 or equivalent 1.5mm 2 core screened Comms OUT 230mm x 160mm x 62mm deep steel enclosure powder coated red - IP54 Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 9...
  • Page 10: Dimensions

    B+80 (140*) (106*) SEDM Actuating mechanism Damper blade Access door/ inspection cover Dimensions with actuating mechanism InMax 50.75S. Flange** ** If it is necessary, arbitrary flange could be removed. Page 10 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 11 Values “e” and “f” - with flange Values "a","c","e" and "f", has to be respected when projecting related smoke exhaust ducts. Flange with corner hole Flanges of dampers are 30 mm wide with oval hole. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 11...
  • Page 12: Technical Parameters

    BELIMO BEN 225 x (15 N.m) 47,7 51,4 0,0264 49,0 52,9 0,0295 50,0 54,0 0,0318 52,5 56,8 0,0380 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 12 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 13 60,8 65,8 0,0714 64,2 69,4 0,0819 67,5 72,9 0,0924 68,3 73,7 0,0945 70,9 76,6 0,1029 72,9 78,8 0,1092 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 13...
  • Page 14 0,1470 84,2 91,0 0,1568 87,8 94,8 0,1691 BELIMO BEE 94,6 102,3 0,1936 (25 N.m) 1000 101,7 109,7 0,2181 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 14 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 15 BELIMO BEN 450 x 58,1 62,9 0,0532 (15 N.m) 60,5 65,4 0,0646 62,0 67,1 0,0722 63,2 68,4 0,0779 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 15...
  • Page 16 74,3 80,1 0,1392 78,3 84,5 0,1632 82,4 88,9 0,1872 86,5 93,3 0,2112 87,4 94,1 0,2160 90,6 97,5 0,2352 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 16 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 17 111,0 0,3127 104,1 111,9 0,3180 107,5 115,5 0,3392 BELIMO BEE 111,8 120,0 0,3657 (25 N.m) 121,6 130,4 0,4187 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 17...
  • Page 18 68,8 70,3 0,0725 BELIMO BEN 700 x (15 N.m) 71,0 72,6 0,0882 73,8 75,4 0,1071 75,6 77,2 0,1197 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 18 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 19 80,6 87,1 0,1666 84,7 91,4 0,1972 89,3 96,2 0,2312 93,8 101,0 0,2652 98,4 105,8 0,2992 99,4 106,8 0,3060 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 19...
  • Page 20 128,6 0,4482 126,2 135,1 0,4897 127,2 136,2 0,4980 BELIMO BE (40 N.m) 131,3 140,4 0,5312 136,3 145,7 0,5727 Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 20 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 21 94,0 100,4 0,1062 BELIMO BEN 1250 x 97,0 103,6 0,1357 (15 N.m) 100,1 106,7 0,1652 103,7 110,4 0,2006 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 21...
  • Page 22 129,6 139,7 0,4147 (25 N.m) 136,3 146,5 0,4862 142,8 153,4 0,5577 150,7 161,5 0,6292 BELIMO BE (40 N.m) Sizes listed within the maximum/minimum sizes can be manufactured on request. Page 22 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 23 185,6 197,8 0,9792 192,5 205,0 1,0557 214,1 227,1 1,2087 SCHISCHEK InMax 50.75 (75 N.m) 1000 228,0 241,4 1,3617 Sizes listed within the maximum/minimum sizes can be manufactured on request. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 23...
  • Page 24: Installation

    ■ With smoke control ducting then refer to duct manufacturers tested parameters for spacing & pattress requirements. ■ No other services should pass through the dampers building work opening. Page 24 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 25: Statement Of Installations

    & EI performance on both sides). The smoke control damper can be integrated into a gypsum wall construction with fire classification EI120 or EI 90. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 25...
  • Page 26: Installation In Solid Wall Construction Of Fire Compartment

    Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing. Page 26 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 27: Installation In Gypsum Wall Construction Of Fire Compartment

    Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing. Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 27...
  • Page 28: Installation In Solid Ceiling Construction Of Fire Compartment

    Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing. Page 28 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 29: Installation In Battery

    Seal all joints (Overplating strips, Spacing strips ■ with SEDM damper) with Promat glue K84. Examples of anchors to the fire dividing con- ■ struction →...
  • Page 30 Seal all joints (Overplating strips, Spacing strips ■ with SEDM damper) with Promat glue K84. Examples of anchors to the fire dividing con- ■ struction →...
  • Page 31 2 dampers on top of each other - solid wall - Ablative Coated Batt system Seal all joints (Overplating strips, Spacing strips ■ with SEDM damper) with Promat glue K84. Examples of anchors to the fire dividing con- ■ struction →...
  • Page 32 EI 120 S 4 dampers - gypsum wall - Ablative Coated Batt system Seal all joints (Overplating strips, Spacing strips ■ with SEDM damper) with Promat glue K84. Examples of anchors to the fire dividing con- ■ struction → see pages 37 to 41 ■...
  • Page 33: Installation Into/Onto Vertical Or Horizontal Smoke Extraction Duct

    → see pages 43 to 44 ■ SEDM Smoke extraction duct Fixing profile with threaded rod → see page 36 Connection´s insulation L-holder → see pages 37 to 41 Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 33...
  • Page 34 → see pages 43 to 44 ■ SEDM Smoke extraction duct Fixing profile with threaded rod → see page 36 Connection´s insulation L-holder → see pages 37 to 41 Page 34 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 35: Suspension Systems

    Coupling Nut M8 - M20 84,3 Anchor Hinge plate - min. thickness 10 mm Concrete screw tested for fire resistance R30-R90, max. Tension up to 0.75 KN (length 35 mm) Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 35...
  • Page 36 Flange of SEDM Flange of duct Self-tapping screw 5x30 mm and 1 pcs large washer M5 (for additional fixing, prevents the damper from sliding off the support - not necessary use) Page 36 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 37 TPM 156/22 Fixing SEDM according to size, with L-holder - tested fixing on wall / ceiling FOR: A < 500 B ≥ 500 FOR: A < 500 B < 500 FOR: A ≥ 500 B ≥ 500 From inner edge of the damper to...
  • Page 38 M8 bolt assemply (bolt min. M8x60 mm, 2 pcs large washer M8, nut M8) or equivalent Anchor → see page 35 Fixing profile with threaded rod → see page 36 Page 38 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 39 TPM 156/22 Fixing SEDM according to size - tested fixing to solid / gypsum or ceiling wall FOR: A < 500 B ≥ 500 FOR: A < 500 B < 500 FOR: A ≥ 500 B ≥ 500 From inner edge of the damper to the center of the holder, on both sides / opposite sides (mirrored) 1 holder to CENTER damper part "A"...
  • Page 40 TPM 156/22 Fixing SEDM to the solid (ceiling) wall construction with Ablative Coated Batt system * ATTENTION TO THE LOCATION OF THE JOINT ! Screws and nuts must not impede the free rotation of Blades. Solid wall construction SEDM Ablative Coated Batt Fixing element/steel holder for connecting damper to the wall (optional accessories MANDIK, a.s.
  • Page 41 SEDM Ablative Coated Batt Fixing element/steel holder for connecting damper to the wall (optional accessories MANDIK, a.s. or sheet metal min. thickness 2 mm and min. width 60 mm) Screw UNI 6x60 mm Installation hols The method of mounting must meet the ■...
  • Page 42: Example Of Duct Connection

    M8 bolt assemply (bolt M8x20 mm, 2 pcs large washer M8, nut M8) * Ceramic self-adhesive tape (FJ 120 Pyrosil B 170-250 kg/m - Tremco-illbruck) or equivalent Lock washers Page 42 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 43 TPM 156/22 Example of connection SEDM damper in steel duct MULTI with insulation ROCKWOOL FIREPRO DuctRock Slab Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with screws and welding pins at max. spacings of 250 mm.
  • Page 44 TPM 156/22 Example installed SEDM damper in fire separating construction and connection to steel duct MULTI Connect the joints of stone wool plates with ROCKWOOL FIREPRO Glue, secure with screws and welding pins at max. spacings of 250 mm. Board joints must be covered using ROCKWOOL black aluminium foil tape. Follow duct supplier's instructions and insulation.
  • Page 45: Accessories

    For KMM grille ensure blade overlaps do not strike KMM- spacer duct may be required - not included in delivery. ■ Free area value for KMM is 78%. ■ SEDM with cover grille without flange SEDM with cover grille and with flange Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 45...
  • Page 46: Technical Data

    → see page 47 Determination of pressure loss by using diagram ρ = 1,2 kg/m air flow speed w [m/s] Page 46 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 47 0,3179 0,3043 0,2975 0,2805 0,2669 1500 0,3791 0,3706 0,3485 0,3400 0,3298 0,3247 0,3162 0,3026 0,2958 0,2788 0,2652 1600 0,3774 0,3672 0,3451 0,3383 0,3264 0,3230 0,3145 0,2992 0,2941 0,2771 0,2635 Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 47...
  • Page 48: Noise Data - Level Of Acoustic Output Corrected With Filter A

    180 200 225 250 280 300 315 355 400 450 500 550 560 600 630 650 700 710 750 800 900 1000 1000 43 1100 42 1250 42 1400 42 1500 42 1600 42 Page 48 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 49 180 200 225 250 280 300 315 355 400 450 500 550 560 600 630 650 700 710 750 800 900 1000 180 >55 200 >55 225 >55 250 >55 1000 49 1100 49 1250 49 1400 48 1500 48 1600 48 Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 49...
  • Page 50 250 ˃55 ˃55 280 ˃55 ˃55 300 ˃55 ˃55 315 ˃55 355 ˃55 400 ˃55 450 ˃55 1000 55 1100 54 1250 54 1400 54 1500 54 1600 54 Page 50 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 51 250 ˃61 ˃61 ˃61 280 ˃61 ˃61 300 ˃61 315 ˃61 355 ˃61 400 ˃61 450 ˃61 1000 58 1100 58 1250 58 1400 58 1500 58 1600 58 Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 51...
  • Page 52 355 ˃63 ˃63 400 ˃63 450 ˃63 500 ˃63 550 ˃63 560 ˃63 600 ˃63 630 ˃63 650 ˃63 1000 62 1100 62 1250 62 1400 62 1500 62 1600 62 Page 52 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 53 630 ˃65 ˃65 650 ˃65 ˃65 700 ˃65 ˃65 710 ˃65 ˃65 750 ˃65 ˃65 800 ˃65 900 ˃65 1000 ˃65 1100 ˃65 1250 ˃65 1400 ˃65 1500 ˃65 1600 ˃65 Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 53...
  • Page 54: Material, Finishing

    Dampers must be protected against impact when Another required packaging system should be approved ■ transported and manipulated. and agreed by manufacturer. Packaging material is not Page 54 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 55: Assembly, Attendance And Maintenance

    Seal up the space around cable with fire resistant mastic (HILTI CFS-S ACR, PROMASTOP) or equivalent. ■ Let the mastic harden. ■ example drilled holes Example of position of holes in the wall of the box, without pre-manufactured slot Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 55...
  • Page 56: Connection Of The Control Module Mdpm & Mdcm Interfaces Inside Protection Box

    For installation, drill 4 holes in the rear of the housing (from inside to outside) with a maximum hole diameter of 8,5mm, ■ use fixing appropriate for the application. Seal all holes and gap between FIRE RATED housing and wall with firestop (HILTI CFS-S ACR, PROMASTOP). Page 56 Multi compartment smoke control damper - SEDM Version 2024-06-26...
  • Page 57: Entry Into Service And Revisions

    Dampers blades should open and close correctly and op- eration should be visually inspected and documented prior to handover. Inspection hole detail Version 2024-06-26 Multi compartment smoke control damper - SEDM Page 57...
  • Page 58: Ordering Information

    P - with flanges design size AxB EXAMPLE: SEDM 180x355 .44/P - 180x355-damper size, .44-damper design, P-with flanges Dampers design Additional digit with actuating mechanism BEN, BEE, BE, InMax 50.75-S for 230V with actuating mechanism BEN, BEE, BE, InMax 50.75-S for 24V with actuating mechanism BEN (BEE)-SR for 24V .65*...
  • Page 59 Manufacturer MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz Authorized representative MANDIK UK Ltd • 130 Aztec West • Bristol BS32 4UB • United Kingdom • Tel.: +44 117 4526376 • E-Mail: help@mandik.co.uk...