These technical specifications state a row of manufactured sizes and models of round smoke extraction dampers - single (further only dampers) SEDS-R. It is valid for production, designing, ordering, delivery, maintenance and operation. 1. Description......................... 2. Design..........................3. Dimensions, weights......................
• External Casing leakage min. class B, Over blade min. class 4, diameter 100 min. class 3 • Cycling test in class C 10000 acc. to EN 12101-8 • ES Certificate No. 1391-CPR-2016/0143 • Declaration of Perfomance No. PM/SEDS-R/01/20/1 • Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19c...
Temperature in the place of installation is permitted to range from - 30°C to + 50°C. Design with actuating mechanism SEDS-R is equipped by actuating mechanism Belimo BLE24 for 24V supply or BLE230 for 230V supply. After being connected to power supply the actuating mechanism displaces the damper blade into operation position "OPEN"...
Page 5
<3° <87° Parrallel connection of other driver is possible. Pay attention to the power input data. Nominal voltage AC 24V 50/60Hz AC 230 V 50/60Hz DC 24 V Power consumption - motoring 7,5 W - holding < 0,5 W < 1 W Dimensioning 9 VA (Imax 2,7 A @ 5 ms) 12 VA (Imax 6 A @ 5 ms)
Page 7
Nominal voltage AC 230V 50/60Hz Power consumption 10 W (including actuating mechanism) Dimensioning 19 VA (including actuating mechanism) Degree of protection Ambient temperature range - 30 °C … + 50 °C Non-operating temperature - 40 °C … + 80 °C Connecting - net cable 1 m without plug - actuator...
For damper (Fig. 9) the open damper blade overlaps the damper body from dimension D = 315 by the value “a” or “a” and “c”. These values are specified in the Tab. 3.2.1. Values "a" and "c" has to be respected when projecting related smoke exhaust ducts. Smoke extraction dampers single are designed to remove heat and combustion products (e.g.
Page 10
Installation examples Position: Damper hinge Holder L Threaded rod Washer Screw connection Profile 30x30...
Pressure loss calculation [Pa] presure loss [m.s ] air flow speed in nominal damper section [kg.m ] air density coefficient of local pressure loss for the nominal damper section (see Tab. 6.1.1.) Determination of pressure loss by using diagram = 1,2 kg.m Coefficient of local pressure loss (-) 1,111 0,930...
Damper casing and damper blade are made of galvanized plate without any other surface finish. Fasteners are galvanized. The appliance is constructed and preset by the manufacturer, its operation is dependent on proper installation and adjustment. Dampers are transported by box freight vehicles without direct weather impact, there must not occur any shocks and ambient temperature must not exceed + 40 °C.
For electrical connection of the actuator use the prefabricated slot in the protection box on the top side of the box. If it is necessary to use other position of the connecting holes, then make two holes to the protection box to pull in connecting cables (heat resistant cables) to the cables of damper´s actuator.
Product label is placed on the damper casing MANDÍK, a.s. Dobříšská 550, 267 24 Hostomice, Czech Republic DIMENSION: ACTUATING SYSTEM: WEIGHT (kg): YEAR/SER.NO.: MANUAL FIRE PROTEC. CLASS: TPM 120/16 EN 12101-8:2011 Cert. No.: 1391-CPR-2016/0143, DoP: PM/SEDS-R/01/20/1 1391 technical specifications design according chapter 2.1 and 2.2 size type...
Page 16
MANDÍK, a.s. Dobříšská 550 26724 Hostomice Czech Republic Tel.: +420 311 706 706 E-Mail: mandik@mandik.cz www.mandik.com The producer reserves the right for innovations of the product. For actual product information see www.mandik.com...