Mandik SEDS-R Manual

Mandik SEDS-R Manual

Round smoke extraction damper-single
Hide thumbs Also See for SEDS-R:

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for Mandik SEDS-R

  • Page 2: Table Of Contents

    These technical specifications state a row of manufactured sizes and models of round smoke extraction dampers - single (further only dampers) SEDS-R. It is valid for production, designing, ordering, delivery, maintenance and operation. 1. Description......................... 2. Design..........................3. Dimensions, weights......................
  • Page 3: Description

    • External Casing leakage min. class B, Over blade min. class 4, diameter 100 min. class 3 • Cycling test in class C 10000 acc. to EN 12101-8 • ES Certificate No. 1391-CPR-2016/0143 • Declaration of Perfomance No. PM/SEDS-R/01/20/1 • Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19c...
  • Page 4: Design

    Temperature in the place of installation is permitted to range from - 30°C to + 50°C. Design with actuating mechanism SEDS-R is equipped by actuating mechanism Belimo BLE24 for 24V supply or BLE230 for 230V supply. After being connected to power supply the actuating mechanism displaces the damper blade into operation position "OPEN"...
  • Page 5 <3° <87° Parrallel connection of other driver is possible. Pay attention to the power input data. Nominal voltage AC 24V 50/60Hz AC 230 V 50/60Hz DC 24 V Power consumption - motoring 7,5 W - holding < 0,5 W < 1 W Dimensioning 9 VA (Imax 2,7 A @ 5 ms) 12 VA (Imax 6 A @ 5 ms)
  • Page 7 Nominal voltage AC 230V 50/60Hz Power consumption 10 W (including actuating mechanism) Dimensioning 19 VA (including actuating mechanism) Degree of protection Ambient temperature range - 30 °C … + 50 °C Non-operating temperature - 40 °C … + 80 °C Connecting - net cable 1 m without plug - actuator...
  • Page 8: Dimensions, Weights

    Dimensions Damper body Damper blade Actuating mechanism cover Installation flange Weights and effective area 0,0061 BELIMO BLE (15 N.m) 10,5 0,0100 BELIMO BLE (15 N.m) 0,0172 BELIMO BLE (15 N.m) 11,5 0,0222 BELIMO BLE (15 N.m) 0,0278 BELIMO BLE (15 N.m) 0,0446 BELIMO BLE (15 N.m) 13,5...
  • Page 9: Placement And Assembly

    For damper (Fig. 9) the open damper blade overlaps the damper body from dimension D = 315 by the value “a” or “a” and “c”. These values are specified in the Tab. 3.2.1. Values "a" and "c" has to be respected when projecting related smoke exhaust ducts. Smoke extraction dampers single are designed to remove heat and combustion products (e.g.
  • Page 10 Installation examples Position: Damper hinge Holder L Threaded rod Washer Screw connection Profile 30x30...
  • Page 11: Pressure Loss

    Pressure loss calculation [Pa] presure loss [m.s ] air flow speed in nominal damper section [kg.m ] air density coefficient of local pressure loss for the nominal damper section (see Tab. 6.1.1.) Determination of pressure loss by using diagram = 1,2 kg.m Coefficient of local pressure loss (-) 1,111 0,930...
  • Page 12: Noise Data And Pressure Loses

    842 1122 1403 1683 1964 2244 2525 2806 1069 1425 1782 2138 2494 2851 3207 3563 1357 1810 2262 2714 3167 3619 4072 4524 1716 2289 2861 3434 4006 4578 5150 5722 905 1018 1131 2121 2827 3534 4241 4948 5655 6362 7069 884 1060 1237 1414 1590 1767 2659 3545 4431 5317 6203 7090 7976 8862 886 1108 1329 1551 1773 1994 2216...
  • Page 13: Material

    Damper casing and damper blade are made of galvanized plate without any other surface finish. Fasteners are galvanized. The appliance is constructed and preset by the manufacturer, its operation is dependent on proper installation and adjustment. Dampers are transported by box freight vehicles without direct weather impact, there must not occur any shocks and ambient temperature must not exceed + 40 °C.
  • Page 14: Entry Into Service And Revisions

    For electrical connection of the actuator use the prefabricated slot in the protection box on the top side of the box. If it is necessary to use other position of the connecting holes, then make two holes to the protection box to pull in connecting cables (heat resistant cables) to the cables of damper´s actuator.
  • Page 15: Product Label

    Product label is placed on the damper casing MANDÍK, a.s. Dobříšská 550, 267 24 Hostomice, Czech Republic DIMENSION: ACTUATING SYSTEM: WEIGHT (kg): YEAR/SER.NO.: MANUAL FIRE PROTEC. CLASS: TPM 120/16 EN 12101-8:2011 Cert. No.: 1391-CPR-2016/0143, DoP: PM/SEDS-R/01/20/1 1391 technical specifications design according chapter 2.1 and 2.2 size type...
  • Page 16 MANDÍK, a.s. Dobříšská 550 26724 Hostomice Czech Republic Tel.: +420 311 706 706 E-Mail: mandik@mandik.cz www.mandik.com The producer reserves the right for innovations of the product. For actual product information see www.mandik.com...

Table of Contents