1MRS757644 H
3.1.2

Analog input settings, residual current

Table 7: Analog input settings, residual current
Parameter
Values (Range)
Primary current
1.0...6000.0
Secondary current
1=0.2A
2=1A
3=5A
Amplitude Corr
0.9000...1.1000
Reverse polarity
0=False
1=True
Angle correction
-8.000 ... 8.000
3.1.3

Analog input settings, phase voltages

Table 8: Analog input settings, phase voltages
Parameter
Values (Range)
1
Primary voltage
0.100...440.000
Secondary voltage
60...210
VT connection
1=Wye
2=Delta
3=U12
4=UL1
Amplitude Corr A
0.9000...1.1000
Amplitude Corr B
0.9000...1.1000
Amplitude Corr C
0.9000...1.1000
2
Division ratio
1000...20000
Voltage input type
1=Voltage trafo
3=CVD sensor
Table continues on the next page
1
For VT
2
For sensor
620 series
Technical Manual
Unit
Step
A
0.1
0.0001
deg
0.0001
Unit
Step
kV
0.001
V
1
0.0001
0.0001
0.0001
1
Basic functions
Default
Description
100.0
Primary current
2=1A
Secondary current
1.0000
Amplitude correc-
tion
0=False
Reverse the polari-
ty of the residual
CT
0.0000
Angle correction
factor
Default
Description
20.000
Primary rated volt-
age
100
Secondary rated
voltage
2=Delta
Voltage transducer
measurement con-
nection
1.0000
Phase A Voltage
phasor magnitude
correction of an
external voltage
transformer
1.0000
Phase B Voltage
phasor magnitude
correction of an
external voltage
transformer
1.0000
Phase C Voltage
phasor magnitude
correction of an
external voltage
transformer
10000
Voltage sensor divi-
sion ratio
1=Voltage trafo
Type of the voltage
input
51