Type Conversion Function Blocks; Qty_Good Function Block; Qty_Bad Function Block - ABB RELION 620 Series Technical Manual

Protection and control
Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 H
3.15.8.3
Signals
Table 78: GOOSERCV_INT32 Output signals
Name
OUT
VALID
3.16

Type conversion function blocks

3.16.1

QTY_GOOD function block

3.16.1.1
Function block
Figure 64: Function block
3.16.1.2
Functionality
The good signal quality function QTY_GOOD evaluates the quality bits of the input
signal and passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function
output, binary input, application function output or received GOOSE signal). Due
to application logic quality bit propagation, each (simple and even combined) signal
has quality which can be evaluated.
The OUT output indicates quality good of the input signal. Input signals that have no
quality bits set or only test bit is set, will indicate quality good status.
3.16.1.3
Signals
Table 79: QTY_GOOD Input signals
Name
IN
Table 80: QTY_GOOD Output signals
Name
OUT
620 series
Technical Manual
Type
INT32
BOOLEAN
Type
Default
Any
0
Type
BOOLEAN
Basic functions
Description
Output signal
Output signal
Description
Input signal
Description
Output signal
145