1MRS757644 H
Parameter
Values (Range)
Description
Operation mode
0=Pulsed
1=Toggle/Persistent
-1=Off
Pulse length
10...3600000
Description
3.17.13

Local generic control points SPCLGAPC

3.17.13.1
Function block
Figure 110: Function block
3.17.13.2
Functionality
The local generic control points function SPCLGAPC is dedicated only for local
controlling, that is, SPCLGAPC cannot be controlled remotely. The local control is
done through the buttons in the front panel.
3.17.13.3
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
SPCLGAPC has the
to control all 16 outputs. By default, the
disables the controllable signal output. SPCLGAPC also has a general setting
Rem restriction , which enables or disables the local or remote state functionality.
When the
between "True" and "False" for every input pulse received. The state of the output is
stored in a nonvolatile memory and restored if the protection relay is restarted.
When the
to produce the predefined length of pulses. Once activated, the output remains
620 series
Technical Manual
Unit
Step
ms
10
Operation mode , Pulse length and Description settings available
Operation mode is set to "Toggle", the corresponding output toggles
Operation mode is set to "Pulsed", the corresponding output can be used
Default
Description
SPCRGAPC1 Output
Generic control point description
15
-1=Off
Operation mode for generic con-
trol point
1000
Pulse length for pulsed operation
mode
SPCRGAPC1 Output
Generic control point description
16
Operation setting. The
Operation mode setting is set to "Off". This
Basic functions
Loc
199