Signals - ABB RELION 620 Series Technical Manual

Protection and control
Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Basic functions
"Latched-S": Latched, ON
This mode is a latched function. At the activation of the input signal, the alarm
shows a steady light. After acknowledgement by the local operator pressing any key
on the keypad, the alarm disappears.
Activating
signal
LED
Acknow.
Figure 27: Operating sequence "Latched-S"
"LatchedAck-F-S": Latched, Flashing-ON
This mode is a latched function. At the activation of the input signal, the alarm
starts flashing. After acknowledgement, the alarm disappears if the signal is not
present and gives a steady light if the signal is present.
Activating
signal
LED
Acknow.
Figure 28: Operating sequence "LatchedAck-F-S"
3.4.3

Signals

Table 28: Input signals
Name
OK
ALARM
RESET
OK
ALARM
RESET
OK
ALARM
Table continues on the next page
86
Type
Default
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
1MRS757644 H
Description
Ok input for LED 1
Alarm input for LED 1
Reset input for LED 1
Ok input for LED 2
Alarm input for LED 2
Reset input for LED 2
Ok input for LED 3
Alarm input for LED 3
620 series