Analog Input Settings, Residual Voltage - ABB RELION 620 Series Technical Manual

Protection and control
Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Basic functions
Parameter
Values (Range)
Angle Corr A
-8.000 ... 8.000
Angle Corr B
-8.000 ... 8.000
Angle Corr C
-8.000 ... 8.000
3.1.4

Analog input settings, residual voltage

Table 9: Analog input settings, residual voltage
Parameter
Values (Range)
Primary voltage
0.100 ... 440.000
Secondary voltage
60...210
Amplitude Corr
0.9000 ... 1.1000
Angle correction
-8.000 ... 8.000
1
In 9-2 applications, Primary voltage maximum is limited to 126 kV.
52
Unit
Step
deg
0.0001
deg
0.0001
deg
0.0001
Unit
Step
1
kV
0.001
V
1
0.0001
deg
0.0001
1MRS757644 H
Default
Description
0.0000
Phase A Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
0.0000
Phase B Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
0.0000
Phase C Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
Default
Description
11.547
Primary voltage
100
Secondary voltage
1.0000
Amplitude correc-
tion
0.0000
Angle correction
factor
Technical Manual
620 series