42 Electrical planning guidelines

Residual current device compatibility

The drive is suitable for use with residual current devices of Type B.
Note: As standard, the drive contains capacitors connected between the main circuit
and the frame. These capacitors and long motor cables increase the ground leakage
current and may cause nuisance faults in residual current devices.

Multidrives modules

The drive is equipped with an internal ground fault protective function to protect the
unit against ground faults in the motor and motor cable. This function is not a
personnel safety or a fire protection feature. See the firmware manual for more
information.
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
Note: As standard, the drive contains capacitors connected between the main circuit
and the frame. These capacitors and long motor cables increase the ground leakage
current and may cause nuisance faults in circuit breakers.

Implementing the Emergency stop function

For safety reasons, install the emergency stop devices at each operator control station
and at other operating stations where emergency stop may be needed. Implement
the emergency stop according to relevant standards.

Cabinet-installed multidrives

You can order the drive with an emergency stop function (option).
See the appropriate option manual for more information.
Name
Emergency stop, stop category 0 (option +Q951) for ACS880 multidrives user's
manual
Emergency stop, stop category 1 (option +Q952) for ACS880 multidrives user's
manual
Emergency stop, stop category 0 (option +Q963) for ACS880 multidrives user's
manual
Emergency stop, stop category 1 (option +Q964) for ACS880 multidrives user's
manual
Emergency stop, configurable stop category 0 or 1 (option +Q979) for ACS880
multidrives user's manual

Multidrive modules

For safety reasons, install the emergency stop devices at each operator control station
and at other operating stations where the emergency stop may be needed. Implement
the emergency stop according to relevant standards.
Note: You can use the Safe torque off function of the drive to implement the Emergency
stop function.
Code
3AUA0000119885
3AUA0000119886
3AUA0000119891
3AUA0000119893
3AUA0000145933