Move (8 Pcs) Mvgapc - ABB RELION 620 Series Technical Manual

Protection and control
Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 H
Table 169: SRGAPC Non group settings (Basic)
Parameter
Values (Range)
Reset Q1
0=Cancel
1=Reset
Reset Q2
0=Cancel
1=Reset
Reset Q3
0=Cancel
1=Reset
Reset Q4
0=Cancel
1=Reset
Reset Q5
0=Cancel
1=Reset
Reset Q6
0=Cancel
1=Reset
Reset Q7
0=Cancel
1=Reset
Reset Q8
0=Cancel
1=Reset
3.17.7

Move (8 pcs) MVGAPC

3.17.7.1
Function block
Figure 99: Function block
3.17.7.2
Functionality
The move (8 pcs) function MVGAPC is used for user logic bits. Each input state
is directly copied to the output state. This allows the creating of events from
advanced logic combinations.
MVGAPC can generate user defined events in LHMI when the output description
setting is changed in Configuration > Generic logic > MVGAPC1 > Output x >
Description. MVGAPC can also be used to generate events for IEC 61850 client as
well as Modbus, DNP3 and IEC 60870-5-103 procotols.
620 series
Technical Manual
Unit
Step
Basic functions
Default
Description
0=Cancel
Resets Q1 output
when set
0=Cancel
Resets Q2 output
when set
0=Cancel
Resets Q3 output
when set
0=Cancel
Resets Q4 output
when set
0=Cancel
Resets Q5 output
when set
0=Cancel
Resets Q6 output
when set
0=Cancel
Resets Q7 output
when set
0=Cancel
Resets Q8 output
when set
177