Application Configuration And Control Mode; Authorization; Lhmi Indications; Signals - ABB RELION 620 Series Technical Manual

Protection and control
Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Basic functions
3.7.5

Application configuration and Control mode

The physical outputs from commands to process are blocked with "Blocked" mode.
If physical outputs need to be blocked totally, meaning also commands from the
binary inputs, the application configuration must be used to block these signals.
Blocking scheme uses BEH_BLK output of CONTROL function block.
3.7.6

Authorization

By default,
possible to write test mode by remote client, if it is needed in configuration. This
is done via LHMI only by setting the
IED test > Test mode. Remote operation is possible only when control position of
the relay is in remote position. Local and remote control can be selected with R/L
button or via Control function block in application configuration.
When using the Signal Monitoring tool to force online values, the following
conditions need to be met.
Remote force is set to "All levels"
Test mode is enabled
• Control position of the relay is in remote position
Table 38: Remote test mode
Remote test mode
Off
Maintenance
All levels
3.7.7

LHMI indications

The yellow Start LED flashes when the relay is in "IED blocked" or "IED test and
blocked" mode. The green Ready LED flashes to indicate that the "IED test and
blocked" mode or "IED test" mode is activated.
3.7.8

Signals

Table 39: PROTECTION input signals
Name
BI_SG_2
BI_SG_3
Table continues on the next page
96
Test mode and Control mode can only be changed from LHMI. It is
61850-8-1-MMS
No access
Command originator category mainte-
nance
All originator categories
Type
BOOLEAN
BOOLEAN
Remote test mode parameter via Tests >
Default
0
0
1MRS757644 H
WHMI/PCM600
No access
No access
Yes
Description
Setting group 2 is ac-
tive
Setting group 3 is ac-
tive
620 series
Technical Manual