Local/Remote Control Function Block Control - ABB RELION 620 Series Technical Manual

Protection and control
Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Basic functions
3.17.10

Local/remote control function block CONTROL

3.17.10.1
Function block
Figure 102: Function block
3.17.10.2
Functionality
Local/Remote control is by default realized through the R/L button on the front
panel. The control via binary input can be enabled by setting the value of the
LR control setting to "Binary input". The binary input control requires that the
CONTROL function is instantiated in the product configuration.
Local/Remote control supports multilevel access for control operations in
substations according to the IEC 61850 standard. Multilevel control access with
separate station control access level is not supported by other protocols than IEC
61850.
The actual Local/Remote control state is evaluated by the priority scheme on the
function block inputs. If more than one input is active, the input with the highest
priority is selected.
The actual state is reflected on the CONTROL function outputs. Only one output is
active at a time.
Table 178: Truth table for CONTROL
CTRL_OFF
TRUE
FALSE
FALSE
FALSE
FALSE
The station authority check based on the IEC 61850 command originator category
in control command can be enabled by setting the value of the
setting to "Station, Remote" (The command originator validation is performed only
if the
in use by default.
1
If station authority is not in use, the CTRL_STA input is interpreted as CTRL_REM.
182
CTRL_LOC
any
TRUE
FALSE
FALSE
FALSE
LR control setting is set to "Binary input"). The station authority check is not
Input
1
CTRL_STA
CTRL_REM
any
any
any
any
TRUE
any
FALSE
TRUE
FALSE
FALSE
1MRS757644 H
Output
OFF = TRUE
LOCAL = TRUE
STATION = TRUE
REMOTE = TRUE
OFF = TRUE
Station authority
620 series
Technical Manual