3.14.2

IEC 61850-9-2 LE sampled values receiving SMVRCV

3.14.2.1
Function block
Figure 53: Function block
3.14.2.2
Functionality
The SMVRCV function block is used for activating the SMV receiving functionality.
3.14.2.3
Signals
Table 64: SMVRCV Output signals
Name
UL1
UL2
UL3
U0
3.14.3

ULTVTR function block

3.14.3.1
Function block
Figure 54: Function block
3.14.3.2
Functionality
The ULTVTR function is used in the receiver application to perform the supervision
for the sampled values and to connect the received analog phase voltage inputs to
the application. Synchronization accuracy, sampled value frame transfer delays and
missing frames are being supervised.
620 series
Technical Manual
Type
Description
INT32-UL1
IEC61850-9-2 phase 1 voltage
INT32-UL2
IEC61850-9-2 phase 2 voltage
INT32-UL3
IEC61850-9-2 phase 3 voltage
INT32-Uo
IEC61850-9-2 residual voltage
Basic functions