Line Connection Via A Ground-Fault Circuit Interrupter - Siemens SINAMICS S120 Equipment Manual

Booksize power sections
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

2.2.5

Line connection via a ground-fault circuit interrupter

In addition to protection measures against hazardous shock current (e.g. overcurrent trip),
selectively tripping AC/DC-sensitive residual-current circuit-breakers can be used.
Note
A direct connection to a power system with selectively tripping AC/DC-sensitive residual-
current circuit-breakers is only possible with the 5 kW, 10 kW, 16 kW and 36 kW line
modules.
Selectively tripping AC/DC-sensitive residual-current circuit-breakers can be used without
restriction as a protective measure against hazardous shock currents.
Figure 2-6
Booksize Power Sections
Equipment Manual, (GH2), 04.2004 Edition, 6SL3097-2AC00-0BP0
L1
L2
L3
PE
Optional
Fuses
Line contactor
Line filter
(optional)
Line reactor
Line module
Residual-current circuit-breaker (RCCB)
2.2 Line connection variations
Selectively
AC/DC-sensitive
RCCB
U1
V1
W1
DCP DCN
Line Connection Booksize
Further
loads
netz_fi_schutz.vsd
2-7