Line Connection Booksize
2.2 Line connection variations
2.2.4

Operation of the line connection components via an isolating transformer

The isolating transformer converts the network configuration of the system (e.g. IT/TT
system) to a TN system. Additional voltage adaptation to the permissible voltage tolerance
range is possible.
An isolating transformer must be used in the following cases:
• The line voltage is higher than 480 V 3AC + 10%. The voltage must be reduced to a
• The motors are not approved for use in IT/TT systems.
• A residual-current circuit-breaker is required.
• The installation altitude is higher than 2000 m.
• A line filter is envisaged in an IT/TT system.
Figure 2-5
2-6
permissible line connection voltage via an isolating transformer with a suitable
transformation ratio.
L1
L2
L3
PE
Fuses
Isolating
transformer
Fuses
Line
contactor
Line filter
(optional)
Line reactor
Line module
Isolating transformer
N
U1
V1
W1
DCP DCN
Equipment Manual, (GH2), 04.2004 Edition, 6SL3097-2AC00-0BP0
Further
loads
netz_trenntrafo.vsd
Booksize Power Sections