Power Loss Of Components In Rated Operation - Siemens SINAMICS S120 Equipment Manual

Booksize power sections
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Configuration and EMC Booksize
6.7 Information about heat dissipation
6.7.3

Power loss of components in rated operation

The following table shows the power loss for components with internal cooling. The
characteristic values apply for the following conditions:
• Line voltage for line modules 400 V
• Pulse frequency of the motor modules 4 kHz
• Rated pulse frequency of the active line modules 8 kHz
• Operation of components with rated power
Overview: Power loss with internal cooling
Table 6-14
Control units and option boards
CU320
TB30
CBC10
Line filters for active line modules
16 kW
36 kW
55 kW
80 kW
120 kW
Line filters for smart line modules
5 kW
10 kW
Line reactors for active line modules
16 kW
36 kW
55 kW
80 kW
120 kW
Line reactors for smart line modules
5 kW
10 kW
Active line modules
16 kW
36 kW
55 kW
80 kW
120 kW
6-30
Overview: Power loss with internal cooling
Unit
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
Equipment Manual, (GH2), 04.2004 Edition, 6SL3097-2AC00-0BP0
Power loss
20
<3
<10
170
250
350
450
590
5
9
90
160
210
450
590
62
116
260
630
900
1350
2200
Booksize Power Sections