Information Related to Software Settings Fire Systems

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, OTHER INVOLVED PARTIES
FIRE SYSTEM INSTALLATIONS IN THE UNITED STATES: This product incorporates field-programmable
software. In order to comply with the requirements in the Standard for Control Units and Accessories for
Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values
or not used at all as indicated below.
Program feature or
option
Link Supervision
when used as a Sole
Path
Automatic Self-Tests
when used with an
alternate
communication path
AC Failure Condition
(ACFC)/Low Power
Failure (LPF)
No Service Condition
(NSC) delay
*
6 hours is specified in 2013 and later editions of NFPA 72; the 2010 edition specified 24 hours (daily).
TG-7 Dual Path Series Installation & Operating Guide
Permitted
Available settings
in UL 864?
(Y/N)
Y
Disabled, 200 seconds, 5 minutes,
60 minutes
Y
Disabled, 6 hours, Daily, Weekly,
Monthly
Y
Disabled, any number of hours up
to 24
Y
30 seconds, 60 seconds, 3-, 5- 10-,
20-, 30-, 45-, 60-, 1440- minutes
Settings permitted in
UL 864
200 seconds, 5 minutes,
60 minutes
6 hours
1 hour, 2 hours, 3 hours
30 seconds, 60 seconds, 3
minutes
3
56052601
*
Rev B
© 2022 Telguard

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Dual Path Series and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Dual path tg-7Dual path tg-7eDual path tg-7fe

Table of Contents