NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, OTHER INVOLVED PARTIES
FIRE SYSTEM INSTALLATIONS IN CANADA: This product incorporates field-programmable software. In
order to comply with the requirements in the Standard for Equipment for Fire Signal Receiving Centres
and Systems, ULC-S559, certain programming features or options must be limited to specific values or
not used at all as indicated below.
Program feature or option
Link Supervision
End-to-End
Acknowledgement
No Service Condition (NSC)
delay
AC Failure Condition (ACFC)/
Low Power Failure (LPF)
TG-7 Dual Path Series Installation & Operating Guide
Permitted
Possible settings
in ULC-
S559?
(Y/N)
Y
Disabled, 180 seconds
Y
Disabled, Enabled
Y
30 seconds, 60 seconds,
3-, 5- 10-, 20-, 30-, 45-,
60-, 1440- minutes
Y
Disabled, any number of
hours up to 24
4
Settings permitted in
ULC-S559
180 seconds
Enabled
No more than 60 seconds
1 hour, 2 hours, 3 hours
56052601
Rev B
© 2022 Telguard