PROFINET Module
Installation Guide
Byte
Description
48–49
Trip code
50–59
Reserved
60–63
Parameter management
The reset input is normally closed by default. If parameter 7-9 Reset/Enable Logic is set to Normally open, the reported state will be inverted (0 =
1
closed, 1 = open).
7.4 Parameter Management
The PROFINET Module can read parameter values from and write parameter values to the soft starter. The card handles 1 parameter
at a time.
The device references parameters according to their position in the soft starter parameter list. Parameter number 1 corresponds to
parameter 1-1 Command Source. Refer to the VLT® Soft Starter MCD 500 Operating Guide for details of the soft starter parameters.
UNPREDICTABLE BEHAVIOR
Changing the values of the parameters in parameter group 20 Advanced Parameters may cause unpredictable behavior in the soft
starter.
-
Consult the local supplier before adjusting the Advanced Parameters.
7.4.1 Output
Use output bytes 2–5 to read or write a parameter to the soft starter.
Controller⇒Device output bytes are structured as follows:
Table 5: Output Byte Details
Byte
Bits
Details
2
0–7
Parameter number to read/write
3
0
Reserved
1
1 = Read parameter
2
1 = Write parameter
3–7
Reserved
4
0–7
Low byte parameter value to write to the soft starter/0 data values for read
5
0–7
High byte parameter value to write to the soft starter/0 data values for read
7.4.2 Input
Parameter data from the soft starter is reported in bytes 60–63.
Device⇒Controller input bytes are structured as follows.
Table 6: Input Byte Details
Byte
Bits
60
0–7
61
0
1
24 | Danfoss A/S © 2022.11
Bits
0–15
C A U T I O N
Details
Echo parameter number
1 = Invalid parameter number
1 = Invalied parameter value
Details
See the chapter Trip Codes.
See the chapter Parameter Management.
Packet Structures
AN428735951761en-000101 / 175R1188