4.2
Technical Manuals Online! - http://www.tech-man.com
SILENCE
If the Silence Switch is pressed:
• The silenceable Notification Appliance Circuits will be turned OFF.
• The silence LED will be turned ON.
• The piezo sounder will be shut OFF.
• 'System Silenced' message will be stored in the History file.
Upon the occurrence of a subsequent event (alarm or trouble), System Silence is
overridden and the control panel will respond to the new event. The System Silence
switch will be ignored for silenceable waterflow type alarms.
MODE
Pressing the Mode Switch followed by a valid 4-digit numerical code and [ENTER/
STORE] selects one of the six modes of operation.
To enter normal mode from any other mode press MODE then
6676 [ENTER/STORE]
Touch-Tone® phone.
1st EVENT
This switch along with the Up Arrow and Down Arrow keys, is used to display any
presently active alarm and/or fault conditions present in the system. Press the 1st
Event switch at any time to display the first event (alarm and/or trouble) that
occurred.
Use the Down Arrow key to view other events (older) that have occurred and are
active - not cleared yet.
UP ARROW
Use the Up Arrow key to view other events (newer), that have occurred and are
active - not cleared yet.
See individual mode descriptions in other sections of this manual.
Displays
Four 7-segment red LED characters provide visual annunciation of status, events
and messages. A list of messages that may appear on the display in normal mode is
shown below:
d__1
Zone 1 Disabled
d__2
Zone 2 Disabled Zone
d__3
3 Disabled
d__4
Zone 4 Disabled
d__5
Zone 5 Disabled Zone
E__1
1 Enabled
E__2
Zone 2 Enabled
E__3
Zone 3 Enabled
E__4
Zone 4 Enabled
E__5
Zone 5 Enabled
A__1
Alarm Zone 1
A__2
Alarm Zone 2
A__3
Alarm Zone 3
A__4
Alarm Zone 4
A__5
Alarm Zone 5
F__1
Trouble Zone 1
F__2
Trouble Zone 2
F__3
Trouble Zone 3
rES_
System Reset
firealarmresources.com
.
6676 spells NORM on a
F__4
Trouble Zone 4
F__5
Trouble Zone 5
F__A
Annunciator Fault
F__E
Earth Fault
Lo_b
Low Battery
no_b
No Battery
PH_1
Primary C. S. Number Communication Fault
PH_2
Secondary C. S. Number Communication Fault
bEL1
Bell 1 Fault
bEL2
Bell 2 Fault
no_1
Primary Phone Line Fault
no_2
Secondary Phone Line Fault
SUP1
Supervisory Alarm Zone 1
SUP2
Supervisory Alarm Zone 2
SUP3
Supervisory Alarm Zone 3
SUP4
Supervisory Alarm Zone 4
SUP5
Supervisory Alarm Zone 5
_AC_
AC Power Loss
50066 Rev D
5/2/97 P/N 50066:D
41