Secondary Central Station Number Account Code (43-46) is programmed in
addresses 43 - 46 in the same manner as the primary phone number Account Code.
Default entries are all '0s'.
Secondary Central Station Number 24-Hour Test Time (47-50) is programmed
in addresses 47-50 in the same manner as the primary number 24-Hour Test Time.
Default is 00:00 (12:00 midnight).
Secondary Central Station Number 24/12/8/6 Hour Test Time (51) The test
message sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours.
If the message is to be sent every 24 hours, leave the factory default entry of zero. If
other test report times are needed, enter 1=12, 2=8 and 3=6.
Alarm Verification (52)
Alarm verification works only on zones programmed as 2-wire smoke detector
zones. After detecting an alarm, the panel removes power from all zones for 6
seconds, resetting all 2-wire smoke detectors. Power is reapplied and a 12 second
retard period allows detectors to stabilize. During the retard/reset period of 18
seconds, subsequent alarms by the same initiating zone are ignored. An alarm
detected on any other 2-wire detector zone during the retard period will cause
immediate verified alarms. A subsequent alarm on the initiating zone occurring
within the confirmation time will cause a verified alarm. Note: Mixing devices on
zones designated as 2-wire smoke zones is not recommended.
During the alarm verification period, access to other modes of operation is
prevented.
ALARM VERIFICATION PERIOD
0 Sec.
6 Sec.
18 Sec.
120 Sec
Detector Alarm Verification RESET RETARD
CONFIRMATION TIME
Detector Zone Goes Into Alarm
Alarm Ignored
Control Panel Processes Alarm if Same Detector Zone is Still in Alarm
90
120
0
30
60
Different Detector Zone Alarms
Control Panel Immediately Processes Alarm
Figure 3-2: Verification Timing Diagram
Factory Default selection is no verification which is '0'. Entering a '1' enables
verification. Note: Consult local Authority Having Jurisdiction (AHJ) prior to
altering this address.
35
50066 Rev D
5/2/97 P/N 50066:D