Backup Reporting (79) Leaving address 79 at '0' means that reports will be
transmitted to the secondary Central Station phone number only if attempts to
communicate to the primary Central Station phone number are unsuccessful.
Programming a '1' causes all reports to be transmitted to the secondary Central
Station phone number.
Touchtone/Rotary Select (80) A '0' programmed in this address by the factory
triggers Touchtone dialing over both phone lines. Select '1' for rotary dialing.
Make Break Ratio (81) Use this address only if you have chosen '1' for address 80.
The make/break ratio is factory set to '0' which is 67/33, but may be changed to '1'
which is a 62/38 ratio.
Programming Event Codes (82-313)
The type of reports and 'event codes' that are sent to the Central Station are in the
preceding Tables. The selections made for the Primary Central Station Number
Communication Format (address 16) and the Secondary Central Station Number
Communication Format (address 42) automatically program addresses 82-313 with
factory default selections.
Any of the event codes may be changed. Consult your Central Station prior to
altering the event codes. Entering an event code of '0' will cause the communicator to
NOT transmit the report. For the 3+1, 4+1 and 4+1 Express formats or the 4+2
expanded format enter a single zero. For the 4+2 standard or 4+2 Express formats
enter two zeros. Transmission of reports to either or both Central Station phone
numbers may be disabled.
Note the special 'System Abnormal Test Report' event code. This report was added
per new UL DACT requirements. This report is generated in place of the normal test
report when an alarm and/or trouble condition exists at the time the test report is due
to be sent.
Programming the Real-Time Clock
Entering an address greater than 313 will cause a display of the current time. On
initial power up, the clock will start running from the factory setting of 00:01
(military time). The far left digit will be flashing, indicating that this is the first digit
to be programmed.
Hours/Minutes
Select a digit then press [ENTER/STORE]. The digit 2nd from the left will start
flashing. Select a digit then press [ENTER/STORE]. Hours setting is complete. With
the digit 2nd from the right flashing, select a digit then press [ENTER/STORE].
The digit on the far right will start flashing. Select a digit then press [ENTER/
STORE]. Minutes setting is complete. Once the last digit corresponding to the
minutes is entered, the display will show the contents of address '00'. Note: If an
invalid digit is selected (i.e. 3 or higher for the first digit) the FACP piezo will beep
and the digit will continue to blink until a valid entry is made.
Note that the software for the MS-5024 operates the internal clock based upon 60 Hz.
The software for the MS-5024E operates the internal clock based upon 50Hz.
End Programming
Exit Programming Mode by pressing MODE, followed by the 4-digit code
corresponding to an alternate mode of operation, then press [ENTER/STORE].
During Program Mode, if no key is pressed within 10 minutes, the panel will revert to
normal mode.