Configuring parameters
Resetting parameters
Passwords setting
ETS
Note:
Connecting a KNX tool
40 / 60
Siemens
Smart Infrastructure
After entering the correct password, the screen displays as follows. Touch / to
advance or return to the desired parameter and use +/- to select the desired
available value.
Refer to section 3.13.3 for Service level parameters; refer to section 3.13.4 for
Expert level parameters.
The factory setting for the control parameters can be reloaded using P71, by
setting the value to ON. Refer to section 3.13.4 for P71.
For power reset and so on, refer to Data Sheets CE1N3174 and CE1N3175.

3.13.2 Setting and downloading parameters using the tools

Control parameters can be adjusted using the bus, either by downloading them
during commissioning or during normal operation with a tool.
The "User level password" (P29) for entering the Service level and the "Installer level
password" (P99) for entering the Expert level. Both passwords can be modified and
downloaded by using ETS.
ETS is an engineering tool that can be used for commissioning of the RDF880KN...
KNX room thermostats. Device address and application, and control parameters
can be defined and downloaded using ETS.
Refer to section 5.1.1 for ETS programming mode
Parameter settings on the RDF880.. KNX room thermostats are only supported by
ETS4 or higher.
The connection of a KNX commissioning or operating tool to the RDF880KN.. KNX
room thermostats is described in section 4.2.
RDF880KN.. Basic documentation
A6V12318532_en--_a
2021-03-22