Before you start 1.3.1 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.3.2 Quality assurance These documents have been prepared with great care: ·...
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
1) Infrared remote control is to be ordered as separate item 2) Square conduit box e.g. ARG71. Round conduit box min 60 mm diameter and min 40 mm depth 6 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure...
AC 24 V, NC, DC 0…10 V, 1 m Electrothermal actuator, STP63 4884 AC 24 V, NO, DC 0…10 V, 1 m The documents can be downloaded from http://siemens.com/bt/download. 7 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en...
Concurrent display of the current temperature or setpoint in °C and in °F Concurrent display of (parameter P07) is possible on the controller without weekly time program. °C and °F 9 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
AUTO (Comfort or Economy Automatic is the default fan speed in Auto Timer mode. 10 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
This means no protective heating or cooling function and thus risk of frost in the heating mode or risk of overheat in cooling mode! 11 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure...
Page 14
Note: The diagrams above show only the water based fan coil application, but not compressor! Water-based fan coil Use with one or two valves for heating and cooling, heating/cooling with application changeover, heating only, or cooling only. 14 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
2-hour intervals during off-hours. The purge function (parameter P50) must be disabled if the controller is to be used Caution in compressor-based applications. 15 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Page 16
7 seconds (RDF600...: 3 seconds) on the operating mode button If “Auto lock” is configured, then the controller will automatically lock the keypad 30 seconds after the last adjustment. 16 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Available for: 2-pipe, ü ü ü ü 2-pipe & el. heater ü ü ü 4-pipe 17 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Proportional band “Cooling” Control command “Valve” · The diagrams only show the PI thermostat’s proportional part. Notes: · For the fan sequence see section 4.8. 18 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Room temperature setpoint Control command “Valve” or “Compressor” Control command “electrical heater” SDH Switching differential “Heating” SDC Switching differential “Cooling” Dead zone Setpoint differential 19 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Page 20
Dead zone Setpoint differential · The diagrams only show the PI thermostat’s proportional part. Notes: · For the fan sequence see section 4.8. 20 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Control. command “Valve” or “Comp.” Cool SDH Switching differential “Heating” SDC Switching differential “Cooling” Dead zone Heating mode with manual selection Cooling mode with manual selection (P01=2) (P1=2) 21 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Page 22
DC 0…10 V are required). · The diagrams only show the PI thermostat’s proportional part. Notes: · For the fan sequence see section 4.8. 22 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
The demand calculated by PI control from the current room temperature and signal setpoint is provided via Y10 and Y20 to the valve actuator as a continuous DC 0...10 V signal. 23 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
The fan speed controller can control a 3-speed or single-speed fan (selected via control parameter P53). A single-speed fan is connected to terminal Q1, a 3-speed fan to terminals Q1, Q2 and Q3. 24 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure...
Page 25
In case of fan failure, the controller cannot protect the electrical heater against Fan failure overtemperatures. That is why the electrical heater must feature a separate safety device (thermal cutout). 25 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Page 26
“FAN” button. The fan returns to the automatic default mode after each switchover from Comfort to Economy and vice-versa. (RDF400… only) 26 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure...
X1 is factory-set to “Operating mode switchover” (3) and X2 to “Heating/cooling changeover” (2). For more information see section 4.4 “Applications”. 27 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Press + or - to adjust the Comfort mode end time or Economy start time and confirm by pressing 28 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure...
· Select fan modes Automatic or Manual. A buzzer in the thermostat indicates remote control command reception. Infrared remote control can be disabled via parameter P70. 30 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure...
2. Press buttons + and – simultaneously for 4 seconds. Release and press button – again within 2 seconds until the display shows “P01”. 31 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure...
Page 32
· P02 is not available when the controller is commissioned for manual Note heating/cooling changeover P01=2 · Parameter display depends on selected application and function (x) Not available 32 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Page 33
Note that this parameter can be quit only if the setting is CLO:= Y21 active back at “---” and by pressing + and – buttons 33 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure...
After the reset, which takes about 3 seconds, the controller is ready for commissioning by qualified HVAC staff. 34 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en...
· Dispose of the device through channels provided for this purpose. · Comply with all local and currently applicable laws and regulations. 35 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Control output for 0…10 V actuator X1, X2 Multifunctional input for temperature sensor (e.g. QAH11.1) or switch Measuring neutral for sensor and switch 36 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
For US installations use Class 2 rated power supplies. Warning For other installations use circuit breakers with rated current of no more than 10 A. 39 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure...
Page 43
Housing front color RAL 9003 white RAL 9004 black Weight RDF3..., RDF4... 0.220 kg RDF600... 0.150 kg *) The documents can be downloaded from http://siemens.com/bt/download. 43 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Sensor input ........28 Fan operation in dead zone ..26 Service level parameters ....32 Fan overrun ........26 Set the time clock ......31 44 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...
Page 45
Switching differential ..... 10 Universal application .....16 Temperature out of range ... 31 View timers ........30 Temporary setpoint ....... 12 Test ..........32 45 / 46 Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en Smart Infrastructure 2020-02-21...