Name
Service level
P02
User operating mode
profile (mode button)
P05
Sensor calibration (intern,
extern)
P06
Standard temperature
display
P08
Comfort setpoint
P09
Minimum setpoint in
Comfort mode
P10
Maximum setpoint in
Comfort mode
P11
Economy heating setpoint
P14
Keylock function
P16
Buzzer function
P22
Internal r.h. sensor
P23
Calibration internal r.h
sensor
P27
Operating mode settings
after power failure or reset
P28
Timer with delay Off
P29
User level password
Note: Parameter display depends on the selected application and function.
Siemens
Smart Infrastructure

3.13.3 Service level parameters

Factory setting
1 = Auto - Comfort -
Protection
0 K
0 = Room Temperature or
Relative Humidity
21 °C
5 °C
35 °C
15 °C
0
ON = Enable
ON = Enable
0%
0 = Return to Previous
Operating Mode / User
Settings
OFF = Disable
0000
RDF880KN..
Basic documentation
Range
1 = Auto - Comfort - Protection
2 = Auto - Comfort - Economy -
Protection
-5 K...+5 K
0 = Room Temperature or Relative
Humidity
1 = Setpoint for Room
Temperature
P9 to P10
5...P10
(P10 = 40 °C max)
P09...40 °C
(P09 = 5 °C min)
OFF, 5...40 °C
0 = Unlock
1 = Locked
2 = Setpoint
OFF = Disable
ON = Enable
OFF = Disable
ON = Enable
±20%
0 = Return to Previous Operating
Mode / User Settings
1 = Protection Mode
OFF = Disable (do not display
Delay Timer Mode symbol)
ON = Enable (display Delay Timer
Mode symbol)
0000 - 9999
Resolution
0.5 K
0.5 K
0.5 K
0.5 K
0.5 K
1%
1 hour
41 / 60
A6V12318532_en--_a
2021-03-22