Control outputs overview
(setting via DIP switches 4 / 5 and parameters P46 / P47)
Control outputs
With RDG100 and RDG100T, the function of the control outputs (2-position or 3-
position) is set via DIP switches 4 and 5 .
With RDG140 and RDG160, DIP switches 4 and 5 can be used to invert the
DC 0...10 V signal to 10...0 V.
The patterns of DIP switches 4 and 5 are as follows:
ON
ON
OFF
OFF
1
2
3
4
5
2-position
2-position
DC 0...10 V
DC 0...10 V
RDG100, RDG100T:
If 2-position is selected, the factory setting is on/off. If you want PWM (pulse width
modulation), set parameters P46 and / or P47 to 2 = PWM.
RDG110: Only on/off available.
For details concerning connection of peripheral devices and setting of the DIP
switches, refer to the Mounting Instructions:
– [4] M3181.1 (RDG100, RDG100T)
– [5] M3181.2 (RDG110)
– [6] M3181.3 (RDG140, RDG160)
RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation
Functions
www.heronhill.co.uk
ON
OFF
1
2
3
4
5
1
2
2-position
3-position
DC 0 ... 10 V
DC 10 ... 0 V inv.
( ) *
* (only possible for 1 actuator)
ON
OFF
3
4
5
1
2
3
4
3-position
3-position
2-position
3-position
DC 10 ... 0 V inv.
10 ... 0 V inv.
DC 0 ... 10 V
10 ... 0 V inv.
CE1P3181en
28 May 2009
Fax: 01823 665807