Control outputs configuration (setting via DIP switches
4/5 or tool, and parameters P46/P47)
Control outputs
The function of the control outputs is set via DIP switches 4 and 5:
ON
OFF
OFF
1
2
3
4
5
Y10 =
DC 0...10 V
2-position
Y1, Y2:
If 2-position is selected, the factory setting is on/off.
If you want PWM (pulse width modulation), set parameter P46 to 2 = PWM.
P47:
 0 = VAV box DC 0...10 V control signal
 1 = VAV box: 3-position control signal
DIP switches 4 and 5 have no impact if the application is commissioned via tool.
Control outputs need to be set via ACS in this case
For details concerning connection of peripheral devices and setting of the DIP
switches, refer to the Mounting Instructions M3192 [3].